YarwaY SerieS AV-5 Air Vent
InstallatIon, operatIon and maIntenance InstructIons
Before installation these instructions must be fully read and understood

SpECIfICatIONS

Pressure-temperature rating:
Shell; ASMe Class 600 (Pn 100) B16.34.
Operating Pressure max.; 600 psig (41 bar).
Operating temperature max.; 650F (343C).
test Pressure max.; 800 psig (55 bar)
nominal Venting Capacity:
1.25 Actual cu ft/min. (0.6 Lit/sec) venting to
atmosphere based on a minimum pressure of
15 psig.
Failure Position:
Vent fails open upon bellows failure.
end Connections:
in-line ½", ¾" nPt (Dn 15, 20) per ASMe
B1.20.1.
installation Position:
Vertical with discharge down.
Special Features:
integral Screen.
All pressures are gauge
Emerson.com/finalControl

applICatION

Series AV-5 vent has been designed to remove
air and non-condensables from steam lines.

OpEratION

the vent operates by means of a thermostatic
bellows which opens and closes an interval
valve in response to temperature changes.
Steam is prevented from discharging through
the vent, and only subcooled non-condensables
are discharged.

MaINtENaNCE

AV-5 vent is permanently assembled; no
maintenance other than flushing or removing
material from the screen is recommended.
Hot discharge from this product may cause severe
burns. Discharge must be piped away or directed
sothat persons in the vicinity are not endangered.
This product must be isolated, vented and cool to
the touch before repairing or inspecting.
AV-5
Conduct
discharge to
safe location
Preferred installation
Acceptable alternative
generally more sensitive
to presence of air
© 2017 emerson. All rights reserved.

trOublEShOOtINg

AV-5 vent is permanently assembled;
no maintenance other than flushing or removing
material from the screen is recommended.
Air vent to pass subcooled gases:
a. Check integral strainer for clogging.
rush or remove material clogging strainer
Air vent blows live steam:
a. Dirt on valve seating area.
b. Worn valve seat. replace the air vent.
c. Failed bellows. replace the air vent.
vent may cycle on
some condensate
VCIOM-03127-EN 18/09

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Yarway Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Emerson Yarway Series

  • Page 1 YarwaY SerieS AV-5 Air Vent InstallatIon, operatIon and maIntenance InstructIons Before installation these instructions must be fully read and understood SpECIfICatIONS applICatION trOublEShOOtINg Pressure-temperature rating: Series AV-5 vent has been designed to remove AV-5 vent is permanently assembled; Shell; ASMe Class 600 (Pn 100) B16.34.
  • Page 2 Automation Solutions, emerson and the emerson logo are trademarks and service marks of emerson electric Co. All other marks are the property of their respective owners.

This manual is also suitable for:

Av-5

Table of Contents