Table 12 - Cooling Setpoint, Programmable Limits And Defaults - York YLAA Series Installation Operation & Maintenance

Air-cooled scroll chillers with brazed plate heat exchanger style b (60 hz) 4-10 fan, 55 - 230 ton, 195 - 700 kw
Table of Contents

Advertisement

SECTION 7 – UNIT CONTROLS

TABLE 12 - COOLING SETPOINT, PROGRAMMABLE LIMITS AND DEFAULTS

SETPOINT KEY
LEAVING CHILLED LIQUID SETPOINT
LEAVING CHILLED LIQUID CONTROL RANGE
RETURNED CHILLED LIQUID SETPOINT
RETURN CHILLED LIQUID CONTROL RANGE
MAX EMS-PWM REMOTE TEMPERATURE
RESET
* See Engineering Guide for operation below 30°F (-1.1°C). Alternate thermal expansion valves must be used below 30°F (-1.1°C).
* When using glycol, Leaving Chilled Liquid Setpoint should not be set below 20°F (-6.7°C).
** Do not exceed 55°F (12.8°C) setpoint before contacting the nearest Johnson Controls Office for application guidelines.
M O N
S T A R T
S T O P
The line under the 0 is the cursor. If the value is wrong,
it may be changed by using the ↑ (UP) and ↓ (DOWN)
arrow keys until correct. Pressing the ENTER/ADV
key will enter the times and then move the cursor to
the minute box. The operation is then repeated if nec-
essary. This process may be followed until the hour,
minutes, and meridian (AM or PM) of both the START
and STOP points are set. After changing the meridian
of the stop time, pressing the ENTER/ADV key will
advance the schedule to the next day.
Whenever the daily schedule is changed
for Monday, all the other days will change
to the new Monday schedule. This means
if the Monday times are not applicable
for the whole week then the exceptional
days would need to be reprogrammed to
the desired schedule.
To page to a specific day, press the SCHEDULE/AD-
VANCE DAY key until the desired day appears. The
start and stop time of each day may be programmed
differently using the ↑ (UP) and ↓ (DOWN) arrow, and
ENTER/ADV keys.
126
WATER COOLING
GLYCOL COOLING*
WATER COOLING
GLYCOL COOLING*
=
0 0 : 0 0
A M
=
0 0 : 0 0
A M
MODE
LOW LIMIT
40.0°F
4.4°C
10.0°F
-12.2°C
1.5°F
0.8°C
40.0°F
4.4°C
10.0°F
-12.2°C
4.0°F
2.2°C
2°F
1.0°C
After SUN (Sunday) schedule appears on the display
a subsequent press of the SCHEDULE/ADVANCE
DAY key will display the Holiday schedule. This is a
two part display. The first reads:
H O L
S T A R T
S T O P
The times may be set using the same procedure as de-
scribed above for the days of the week. After chang-
ing the meridian of the stop time, pressing the ENTER/
ADV key will advance the schedule to the following
display:
S __ M
T
H O L I D A Y
The line below the empty space next to the S is the
cursor and will move to the next empty space when
the ENTER/ADV key is pressed. To set the Holiday,
the cursor is moved to the space following the day of
the week of the holiday and the ↑ (UP) arrow key is
pressed. An * will appear in the space signifying that
day as a holiday. The * can be removed by pressing the
↓ (DOWN) arrow key.
The Holiday schedule must be programmed weekly –
once the Holiday schedule runs, it will revert to the
normal daily schedule.
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
HIGH LIMIT
DEFAULT
**70.0°F
44.0°F
21.1°C
6.7°C
**70.0°F
44.0°F
21.1°C
6.7°C
2.5°F
2.0°F
1.4°C
1.1°C
70.0°F
44.0°F
21.1°C
6.7°C
70.0°F
44.0°F
21.1°C
6.7°C
20.0°F
10.0°F
11.1°C
5.6°C
40°F
20°F
22.0°C
11.0°C
=
0 0 : 0 0
A M
=
0 0 : 0 0
A M
W
T
F
S
N O T E D
B Y
JOHNSON CONTROLS
*

Advertisement

Table of Contents
loading

Table of Contents