HBH Physical Data
Model
Compressor Quantity
Number of Circuits (Compressors)
Factory Charge HFC-410a (oz) [kg] per circuit
Blower Motor
Blower Motor Quantity
Standard Motor (hp) [kW]
Large Motor (hp) [kW]
Blower
No. of Blowers
Blower Wheel Size D x W (in) [cm]
Water Connection Size
FPT (in) [mm]
Coax Volume
Volume (US Gallons) [liters]
Condensate Connection Size
FPT (in) [mm]
Air Coil Data
Air Coil Dimensions H x W (in) [cm]
2
2
Air Coil Total Face Area (ft
) [m
]
Miscellaneous Data
Filter Standard - 1" [25.4mm] Throwaway (qty)
(in) [cm]
Weight - Operating (lbs) [kg]
Weight - Packaged (lbs) [kg]
All units have grommet compressor mountings, and 1/2" & 1-3/4" electrical knockouts.
Unit Maximum Water Working Pressure
Base Unit
Weight - Operating (lbs) [kg]
Weight - Packaged (lbs) [kg]
Weight - Corner - Control box/Compressor side (lbs) [kg]
Weight - Corner - Compressor side (lbs) [kg]
Weight - Corner - Blower side (lbs) [kg]
Weight - Corner - Air Coil side (lbs) [kg]
HBH SERIES
072
096
Scroll
2
60 [1.70]
76 [2.15]
1
1 [0.75]
2 [1.49]
2 [1.49]
3 [2.24]
1
12 x 12 [30.48 x 30.48]
1-1/4" [31.8]
1.62 [6.13]
1.81 [6.85]
3/4" [19.1]
20 x 54 [50.8 x 137.2]
20 x 64 [50.8 x 162.6]
7.5 [0.70]
(QTY.4) 16 x20 [40.6 x 50.8]
586 [265.8]
644 [292.1]
626 [283.9]
684 [310.3]
Max Pressure PSIG [kPa]
300 [2068]
HBH072
HBH096
586 [265.8]
644 [292.1]
626 [283.9]
684 [310.3]
235 [106.6]
254 [115.2]
101 [45.8]
120 [54.4]
180 [81.6]
190 [86.2]
70 [31.8]
80 [36.3]
18
120
80 [2.27]
3 [2.24]
5 [3.73]
1-1/2" [38.1]
2.40 [9.08]
8.9 [0.83]
698 [316.6]
738 [334.8]
HBH120
698 [316.6]
738 [334.8]
271 [122.9]
137 [62.1]
200 [90.7]
90 [40.8]