OPEN CIRCUIT THERMOCOUPLE TESTING
Step 1.
Disconnect thermocouple from gas control.
Step 2.
Using a multimeter capable of measuring millivolts, connect
one alligator clip to the end ball or contact portion of the
thermocouple, and the other alligator clip to copper portion of
the thermocouple.
Step 3.
Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for
three minutes. A reading of 20 to 30 millivolts indicates good thermocouple output.
THERMOCOUPLE REPLACEMENT
Step 1.
Turn off gas supply to water heater. Rotate knob of gas control to "OFF" position.
For White Rodgers gas
control, depress knob
slightly and rotate
clockwise to the "OFF"
position.
Step 2.
Remove outer jacket door.
Step 3.
Slide open inner combustion chamber door.
Step 4.
Disconnect thermocouple from gas control. Locate other end of
thermocouple inside of combustion chamber and remove from pilot bracket. Pull firmly pulling away
from the pilot assembly.
Step 5.
Install new thermocouple into pilot bracket making certain the thermocouple is fully engaged into the pilot
bracket. Connect other end of thermocouple to gas control (finger tight + ¼ turn).
Step 6.
Route carefully through the relief opening in the combustion chamber skirt.
Step 7.
To resume operation follow the instructions located on the lighting instruction label or the lighting
instructions located in the installation and operation manual.
Step 8.
Slide inner door closed when finished.
6
NOTE:
It will be necessary to hold the gas control
knob down in the "PILOT" position
continuously throughout this test.
Figure 2
Page 6
SERVICE PROCEDURE AG-I
Thermocouple Testing and Replacement
For Models Using White Rodgers or
Robertshaw Gas Control
Figure 3
Thermocouple position
Figure 1
For Robertshaw gas
control, rotate knob
clockwise to the "OFF"
position.
Figure 4