3. Mini VRF System Alarm Codes
P16 Overcurrent of Inverter Compressor
1.
Meaning of Alarm
Secondary current effective value detected the overcurrent (trip current value).
Single-phase model : Trip current = 24.0 A
Secondary current instantly detected over xx A.
Single-phase model : xx A = 45.0 A
2.
Check of content
0 Multiple
Replaced the compressor (added oil, if it was necessary)
0-1
factors
but it occurred again immediately.
0-2
Replaced the board, but it occurred again immediately.
1 Power
1-1
Power cord connections are loose.
Source
Rated power voltage is not within + 10%.
1-2
1-3 Extreme fluctuations in voltage.
1-4 An open phase state is observed.
2 Board
Disconnected parts, miswiring and/or poor connections (loose)
wiring
are observed in the connections on the CR board and/or in the
2-1
connections of components that are connected by wiring from
the CR board.
Disconnected parts, miswiring and/or poor connections (loose)
2-2
are observed in the connections of outdoor board(s) that are
connected by wiring from the CR board.
Disconnected parts, miswiring and/or poor connections (loose)
2-3
are observed in the connections of outdoor board(s) that are
connected by wiring from the HIC board.
Disconnected parts, miswiring and/or poor connections (loose)
2-4
are observed in the connections of HIC boards connected by
wiring from the CR board.
Disconnected parts, miswiring and/or poor connections (loose)
2-5
are observed in the connections of HIC board(s) that are
connected by wiring from the outdoor board.
Disconnected parts, miswiring and/or poor connections (loose)
2-6
are observed in the connections of HIC board(s) that are
connected by wiring to a compressor.
3
Disconnections and/or miswiring are observed in the
3-1
Compressor
connecting location of the compressor terminals.
wiring
Conditions such as burned terminal covers and/or discolored
3-2
terminals are observed in the connecting location of the
compressor terminals.
3-phase model : Trip current = 18.0 A
3-phase model : xx A = 36.0 A
3-45
Mini VRF SYSTEM
Trouble Diagnosis
Yes
7-1
No
-
Replace compressor
Yes
along with adding oil,
then recheck from 1-1
No
-
Correct the wiring
Yes
No
1-2
Yes
Test the power supply
No
1-3
Yes
Test the power supply
No
1-4
Yes
Test the power supply
No
2-1
Yes
Correct
No
2-2
Yes
Correct
No
2-3
Yes
Correct
No
2-4
Yes
Correct
No
2-5
Yes
Correct
No
2-6
Yes
Correct
No
3-1
Yes
Correct
No
3-2
Eliminate looseness by
changing the terminals,
Yes
or crimping the
terminals again.
No
4-1
3