3. Mini VRF System Alarm Codes
L10 Outdoor Unit Capacity Not Yet Setup Error
1.
Error Detection Method
It is judged an error when outdoor unit capacity not yet setup or systematically unauthorized setting.
2.
Error Diagnosis
1 Check the
control
1-1
Was EEPROM replaced when PC board was replaced?
PC board
2 Installation
Set an applicable capacity value on the item code 81 display of maintenance remote
or setting
2-1
controller.
related
Check : Connect the outdoor maintenance remote controller and check whether item code 81 outdoor capacity value
shows "0" or unauthorized capacity is set on the detailed setting mode display of the outdoor EEPROM.
If the capacity value of the item code 81 with the outdoor maintenance remote controller is incorrect, recorrect and
set it again.
* After setting the capacity value, be sure to reset the power supply switches of both indoor and outdoor units.
3-37
Mini VRF SYSTEM
Trouble Diagnosis
Yes
2-1
No
Replace EEPROM
3