CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure 
positive (+) must be connected to positive (+) and negative (‐) must be connected to negative (‐). 
 
 

AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker 
between inverter and AC input power source. This will ensure the inverter can be securely 
disconnected during maintenance and fully protected from over current of AC input. The 
recommended spec of AC breaker is 32A for 3KVA and 50A for 5KVA. 
 
There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis‐connect input 
and output connectors. 
WARNING!
All wiring must be performed by a qualified personnel. It's very important for system 
safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of 
injury, please use the proper recommended cable size as below. 
Model 
3KVA 
4/5KVA 
 
PV Connection
 
CAUTION:
Before connecting to PV modules, please install separately a DC circuit breaker 
between inverter and PV modules.
WARNING!
It's very important for system safety and efficient operation to use appropriate cable 
for PV module connection. To reduce risk of injury, please use the proper recommended cable 
size as below. 
 
Model 
3‐5KVA 
 
Gauge
12 AWG
10 AWG
Wire Size
12AWG
Cable (mm2)
4
6
Cable (mm2)
Torque value(max)
4
 
Torque Value 
1.2 Nm 
1.2 Nm 
1.2 Nm 