3.3.8.

Calibration incomplete

If the calibration is not completed the display will continually flash the "incomplete calibration" error (section 3.1.3),
during all subsequent power cycles. This indicates that a calibration was attempted but never completed.
Recalibrate the display completely to remove this error condition.
3.4.

Self test

The ITL40 can check its hardware for proper operation by entering the password RLLR LLRR.
The display will turn all the LEDs ON and then cycle each LED OFF individually starting with the top LED. All LEDs
will come on and begin flashing between full bright and the calibrated dim level for 5 seconds. The display will then
scroll text indicating the self test condition.
Memory test
"MEM-PASS"
"MEM-FAIL"
Sensor signal test (MASTER unit only)
"SIG-PASS"
"SIG-FAIL"
Communication wire test
'WIRE-PASS"
"WIRE-FAIL"
If the self test password is used on a MASTER display all REMOTE displays will also perform their self test.
3.5.

Setting the dim LED level

The display can be dimmed by applying system power to pin 4 (Dim Display input). The ITL40 has 9 levels of
brightness available (9 = brightest, 1 = dimmest, default value is 3).
To select the dim level of the display use the magnetic switches to enter the password RLLR LLLR.
All of the LEDs will be illuminated during the set-up. Touch a magnet against the RIGHT switch and the display will
dim to the next level and show the dim value number (9 through 1). Release the magnet and again touch it against
the RIGHT switch again to drop to the next dim level. Once the dim level is at the dimmest setting (1) the next touch
of the magnet will cycle to the highest dim level (9).
When the dim level is at the desired point activate the LEFT switch to save and exit.
3.6.

Show software version, device settings, and errors

The ITL40 can display its setting by entering the password RRRR RRRR.
The display will scroll the software version, unit type, communication method, and then display any errors.
Software version
"Vx.x"
Unit type
"MASTER"
"REMOTE"
"CAL INCOMPLETE"
"UNKNOWN"
MANUAL P/N:118253
S U I T A B L E F O R E X T E R N A L D I S T R I B U T I O N
OPERATION MANUAL
ITL40
Intelli-Tank Level 40
Memory (EEPROM) is good.
Memory (EEPROM) failure detected.
Sensor signal voltage within tolerance (0.4 volts to 4.8 volts).
Sensor signal voltage out of tolerance (0.4 volts to 4.8 volts).
Data communication lines good.
Data communication lines shorted or open.
Where x.x equals the numeric software version. For example, V1.0.
The unit is set as a MASTER.
The unit is set as a remote.
A calibration was started but never completed.
The unit type cannot be determined – ERROR.
P/N
118404-XX
11 of 27
PAGE
DATE
6/12/2019
REV
1.30
BY
AMS
P
: 6/12/19
RINTED