Page 2
Version 1.4 Application Guide PumpDrive 2 Eco Application Guide PumpDrive 2 Eco The use cases in the application guide are only typical examples for training purposes. The examples are not cus- tomer specific solutions. The examples are not binding and can be incomplete. The examples do not cover all possi- ble eventualities.
Version 1.4 Application Guide PumpDrive 2 Eco Pre-Conditions ..........................3 1.1.1 Pump characteristc curve ............................6 1.1.2 Parameterization of Motor data..........................7 Single pump ..........................8 Single pump – Open loop control ......................8 2.1.1 Open loop control: control value at display ......................8 Open loop control: control value by external signal 0…10V ................
Version 1.4 Application Guide PumpDrive 2 Eco 1. Pre-Conditions The motor data are set according to the operating manual. The motor control is correct selected and suits to the motor. The pump curves are stored in the drive. Pre-settings from production Pumps with PumpDrive are delivered with the following pre-settings: ...
Page 5
Version 1.4 Application Guide PumpDrive 2 Eco Connecting mains and motor Size A (0,37 kW – 1,5 kW) LINE MOTOR Function L1 L2 L3 Mains connection PE U Motor connection MOTOR PTC connection Brake Motor PTC Jumper for IT mains Size B (2,2 kW –...
Page 6
Version 1.4 Application Guide PumpDrive 2 Eco Standard Display For the parameterization of the following applications the user must be logged in Customer Level. Customer Login in Favourite Menu: By pressing the button OK Taste the user selects the Favourite Menu, where the main parameters can be changed.
Version 1.4 Application Guide PumpDrive 2 Eco 1.1.1 Pump characteristic curve The pump characteristic curve for an Etaline 040-040-160 with full impeller diameter 174 has to been set manually. The values for the pump characteristic curves are readout of the type series booklet at nominal speed of the pump with impeller diameter 174.
Version 1.4 Application Guide PumpDrive 2 Eco 1.1.2 Parameterization of Motor data A PumpDrive 2 is parameterized for a 2 pole SuPremE Motor. The pump rotation is clockwise. Name plate of motors: Parameter Change value to Pre-settings by factory Changeable by...
Version 1.4 Application Guide PumpDrive 2 Eco 2. Single pump Single pump – Open loop control 2.1.1 Open loop control: control value at display A fixed speed of 2000 1/min should be set on the display. The nominal speed of the 2 pole motor is 2950 1/min.
Version 1.4 Application Guide PumpDrive 2 Eco 2.1.2 Open loop control: control value by external signal 0…10V A fixed speed of 2000 1/min should be given by an external signal 0…10V at analog input 1. 2000 1/min is equal to 6,78 V when using a 2-pole motor with a nominal speed of 2950 1/min.
Version 1.4 Application Guide PumpDrive 2 Eco 2.1.3 Open loop control: control value by external signal 4…20mA A fixed speed of 2000 1/min should be given by an external signal 4…20mA at analog input 1. The feedback of the speed should be send by analog output to a PLC.
Version 1.4 Application Guide PumpDrive 2 Eco 2.1.4 Open loop control: digital motor potentiometer A fixed speed of 2000 1/min should be changeable by the digital inputs with an increment of 10 [1/min]. +/- 2000 1/min PDrv 2 Eco drive...
Version 1.4 Application Guide PumpDrive 2 Eco Single pump – closed loop control 2.2.1 Closed loop control: Differential pressure with PumpMeter (Modbus) A constant differential pressure of 4 bar is needed. PumpMeter is used as a differential pressure sensor in the measurement range of -1 …...
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.2 Closed loop control: differential pressure with sensor 4…20mA A constant differential pressure of 4 bar is needed. The 4…20mA differential pressure sensor with a measurement range of 0-6 bar is connected to analog input 2. The set point is given by the display Δp...
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.3 Closed loop control: differential pressure with sensor 4…20mA set point via analog input A constant differential pressure of 4 bar is needed. The 4…20mA differential pressure sensor with a measurement range of 0-6 bar is connected to analog input 2.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.4 Closed loop control: differential pressure with 2 pressure sensors 4...20 mA A constant differential pressure of 4 bar is needed. A 4…20mA pressure sensor on the high pressure side with a measurement range of 0- 6 bar is connected to analog input 1.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.5 Closed loop control: Sensorless differential pressure control A constant differential pressure of 4 bar is needed without using a sensor. The set point is given by the display. The procedure is based on the characteristic curves of the pump.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.6 Closed loop control: pressure with pressure sensor 4...20 mA A constant pressure of 4 bar is needed. The 4…20mA pressure sensor on the high pressure side with a measurement range of 0-6 bar is connected to analog input 2.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.7 Closed loop control: Pressure with PumpMeter (Modbus) A constant pressure of 4 bar is needed. PumpMeter is used as a pressure sensor in the measurement range of -1 … 10 bar. PumpMeter is connected by Modbus to the M12 Module of the drive.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.8 Closed loop control: Pressure with Pressure sensor 0...10 V A constant pressure of 4 bar is needed. The 0…10V pressure sensor on the high pressure side with a measurement range of 0-6 bar is connected to analog input 2.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.9 Closed loop control: Pressure, Set point (closed loop) at analog input 0…10V A constant pressure of 4 bar is needed. A 4…20mA pressure sensor on the high pressure side with a measurement range of 0-6 bar is connected to analog input 2.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.10 Closed loop control: constant level at low pressure side with submersible sensor 4…20mA A constant level of 2 m is needed in a tank on the suction side. The 4…20mA level sensor with a measurement range of 0-1 bar is con- nected to analog input 2.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.11 Closed loop control: temperature with thermometer 4…20mA A constant cooling temperature of 50°C is needed. The 4…20mA thermometer on the high pressure side with a measurement range of 0- 150°C is connected to analog input 2. The set point is given by the display.
Version 1.4 Application Guide PumpDrive 2 Eco 2.2.12 Closed loop control: Flow rate with flow rate sensor 4…20mA A constant flow rate of 100 l/min is needed. The 4…20mA flow rate sensor on the high pressure side with a measurement range of 0...200 l/min is connected to analog input 2.
M12 Module: Double and multi pump operation +24V M12 Module: PumpMeter +24V M12 Module female C: Bus resistor M12 Module female D: for Double and multi pump operation (KSB-de- vice bus) Parameter Change value to Pre-settings by factory Changeable by...
Page 26
AIN1 Function M12 Module: Double and multi pump operation +24V +24V M12 Module: PumpMeter M12 Module female C: for Double and multi pump operation (KSB- device bus) M12 Module female D: Bus resistor Parameter Change value to Pre-settings by factory...
M12 Module: Double and multi pump operation AO: OUT 0V(GND) 0V (GND) M12 Module: PumpMeter +24V +24V M12 Module female C: Bus resistor M12 Module female D: for Double and multi pump operation (KSB-de- vice bus) Parameter Change value to Pre-settings by fac- Changeable by tory...
Page 28
Version 1.4 Application Guide PumpDrive 2 Eco Configuration of drive 2: Function Or local Or PLC PDrv2 Eco Drive Enable power electronic Ground for digital inputs System start with DI DI-EN +24V Set point (open loop): 0…10V Alarm DICOM Tailor-made bus cable for double and multi pump operation...
M12 Module: Double and multi pump operation M12 Module: PumpMeter M12 Module female A: connection PumpMeter (Modbus) M12 Module female C: Bus resistor M12 Module female D: for Double and multi pump operation (KSB-de- vice bus) Parameter Change value to...
Page 30
AIN1 Function M12 Module: Double and multi pump operation M12 Module: PumpMeter +24V +24V M12 Module female C: for Double and multi pump operation (KSB-de- vice bus) M12 Module female D: Bus resistor Parameter Change value to Pre-settings by fac-...
Sensor PumpMeter suction side Sensor PumpMeter pressure side M12 12 Module female A: connection PumpMeter (Modbus) M12 Module female C: for Double and multi pump operation (KSB-de- vice bus) or Bus resistor M12 Module female D: for Double and multi pump operation (KSB-de- vice bus) or Bus resistor 2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx...
Page 34
M12 Module: Double and multi pump operation M12 Module: PumpMeter M12 12 Module female A: connection PumpMeter (Modbus) M12 Module female C: Bus resistor M12 Module female D: for Double and multi pump operation (KSB-de- vice bus) Parameter Change value to...
Page 35
Function M12 Module: Double and multi pump operation M12 Module: PumpMeter M12 12 Module female A: connection PumpMeter (Modbus) M12 Module female C: for Double and multi pump operation (KSB-de- vice bus) M12 Module female D: Bus resistor Parameter Change value to...
M12 Module female B: connection cross link bus cable for the redun- Schirm dant connection M12 Module female C: for Double and multi pump operation (KSB-de- vice bus) or Bus resistor Signal M12 Module female D: for Double and multi pump operation (KSB-de- vice bus) or Bus resistor 2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx...
Page 37
M12 Module female B: cross link cable is not necessary if there is an additional sensor connected to the Aux Master. M12 Module female C: Bus resistor M12 Module female D: for Double and multi pump operation (KSB-de- vice bus) Parameter...
Page 38
M12 Module: Double and multi pump operation M12 Module: PumpMeter / Pressure Sensor M12 Module female A: connection pressure sensor M12 Module female D: for Double and multi pump operation (KSB-de- vice bus) M12 Module female C: Bus resistor Parameter...
Version 1.4 Application Guide PumpDrive 2 Eco 4. Pump functionality Closed loop control 4.1.1 Closed loop control: dynamic differential pressure set point compensation based on flow rate estimation A constant differential pressure of 4 bar is needed. PumpMeter is used as a differential pressure sensor in the measurement range of -1 …...
Page 40
Version 1.4 Application Guide PumpDrive 2 Eco 3-5-2-2 Pipe Diameter Discharge Pressure Measur- 30 mm Preset ServiceTool ing Point 3-5-2-3 Height Difference_Pressure Measuring 0,4 m Preset ServiceTool Points 3-5-2-4 Pressure Measuring Point Positions Close to Pump Preset ServiceTool 3-9-3-1 Dynamic Pressure Setpoint Compensation...
Version 1.4 Application Guide PumpDrive 2 Eco 4.1.2 Closed loop control: dynamic differential pressure set point compensation based on speed A constant differential pressure of 4 bar is needed. The 4…20mA differential pressure sensor with a measurement range of 0-6 bar is connected to analog input 2.
Version 1.4 Application Guide PumpDrive 2 Eco 4.1.3 Open loop control: 1 fix speed selected by digital switches or variable speed via analog signal A fixed speed of 2000 1/min should be set on the display. The nominal speed of the 2 pole motor is 2950 1/min.
Version 1.4 Application Guide PumpDrive 2 Eco 4.1.4 Closed loop control: sleep Mode A constant differential pressure of 4 bar is needed. PumpMeter is used as a differential pressure sensor in the measurement range of -1 … 10 bar. PumpMeter is connected by Modbus to the M12 Module of the drive. The set point is given by the display. The frequency in- verter stops the pump without setpoint increase in the case of low flow rates, i.e.
Version 1.4 Application Guide PumpDrive 2 Eco 5. M12 Cable Bus cable for connecting PumpMeter to the M12-Module Tailor-made cable function length Mat.-Nr. tailor-made bus cable for the connection of PumpMeter to 01533775 the M12 Module (color: black, female: straight, male: angled)
Version 1.4 Application Guide PumpDrive 2 Eco Bus cable for Double- and Multi Pump Operation Tailor-made cable function length Mat.-Nr. Tailor-made bus cable for double and multi pump operation 01533747 (color: purple, male: angled, male: angled) 01533748 01533749 01651182 10 m...
Version 1.4 Application Guide PumpDrive 2 Eco Crosslink cable Tailor-made cable: function length Mat.-Nr. tailor-made cross link bus cable for the redundant connection 01533769 of PumpMeter (color: black, female: angled, male: angled) 01533770 01533771 01533772 10 m 01533773 20 m...
Version 1.4 Application Guide PumpDrive 2 Eco M12 Cable for fieldbus module Modbus RTU Tailor-made cables are not available due to individual length. Self-made bus cable for fieldbus module Modbus: 1 2 3 4 5 1 2 3 4 5...
Version 1.4 Application Guide PumpDrive 2 Eco 6. Project Description: PDrv 2 Eco Drive Or local Or PLC DI-EN Function +24V DICOM +24V AO-GND +24V AIN2 +24V AIN1 +24V Parameter Change value to Changeable by 2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx Page 47 of 48...