Ebmpapst CN1116 Operating And Maintenance Instructions Manual page 35

Modbus display & control (mdc)
Table of Contents

Advertisement

Operating and Maintenance Instructions
PID I-Value – Sets the integral value of the controller's PID control algorithm
Address: 19
Availability: Constant Volume/Constant Pressure
Values: 0 to 1000 (default = 30)
NOTE: Value is stored in non-volatile memory in the MDC
PID D-Value – Sets the derivative value of the controller's PID control algorithm
Address: 20
Availability: Constant Volume/Constant Pressure
Values: 0 to 1000 (default = 0)
NOTE: Value is stored in non-volatile memory in the MDC
Controller Uptime High Bytes – Higher 16-bits of the Controller Uptime counter
Address: 21
Controller Uptime Low Bytes – Lower 16-bits of the Controller Uptime counter
Address: 22
NOTE: The Controller Uptime counter is in seconds. This counter will reset at every power cycle.