Table 8 - Controller's Dedicated Modbus Holding Registers Part 2; Table 9 - Direct Access To Individual Fan Holding Registers - Ebmpapst CN1116 Operating And Maintenance Instructions Manual

Modbus display & control (mdc)
Table of Contents

Advertisement

Operating and Maintenance Instructions
IMPORTANT: Do not attempt to read/write more than 6 Modbus registers at a time
210-OMI14229-Iss2
© ebm-papst UK Ltd 2018
ADDR
(hex)
CB00
FAN 1 - FAN RESPONSIVE (1=YES / 0= NO)
CB01
FAN 1 - ALARM REGISTER 1 (SEE APPENDIX F)
CB02
FAN 1 - ALARM REGISTER 2 (SEE APPENDIX F)
CB03
FAN 1 - WARNING REGISTER 1 (SEE APPENDIX F)
CB04
FAN 1 - WARNING REGISTER 2 (SEE APPENDIX F)
CB05
FAN 1 - WARNING REGISTER 3 (SEE APPENDIX F)
CB06
FAN 1 - POWER (W)
CB07
FAN 1 - SPEED (RPM)
CB0A
FAN 1 - RPM LIMIT (RPM)
CB0B
FAN 1 - MOTOR TEMPERATURE (ºC)
CB0C
FAN 1 - ELECTRONICS TEMPERATURE (ºC)
CB0D
FAN 1 - HOURS RUN (hours)
CB0E
FAN 1 - CONTROL (0-100%)
CB80
FAN 2 - FAN RESPONSIVE (1=YES / 0= NO)
CB81
FAN 2 - ALARM REGISTER 1 (SEE APPENDIX F)
CB82
FAN 2 - ALARM REGISTER 2 (SEE APPENDIX F)
CB83
FAN 2 - WARNING REGISTER 1 (SEE APPENDIX F)
CB84
FAN 2 - WARNING REGISTER 2(SEE APPENDIX F)
CB85
FAN 2 - WARNING REGISTER 3 (SEE APPENDIX F)
CB86
FAN 2 - POWER (W)
CB87
FAN 2 - SPEED (RPM)
CB88
FAN 2 - RPM LIMIT (RPM)
CB89
FAN 2 - MOTOR TEMPERATURE (ºC)
CB8A
FAN 2 - ELECTRONICS TEMPERATURE (ºC)
CB8B
FAN 2 - HOURS RUN (hours)
CB8C
FAN 2 - CONTROL (0-100%)
Table 8 – Controller's Dedicated Modbus Holding Registers Part 2
ADDR
(hex)
200
FAN 1 HOLDING REGISTER D000
3FF
FAN 1 HOLDING REGISTER D2FF
400
FAN 2 HOLDING REGISTER D000
5FF
FAN 2 HOLDING REGISTER D2FF
Table 9 – Direct Access to Individual Fan Holding Registers
Operation & Maintenance Instructions
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail
sales@uk.ebmpapst.com
DESCRIPTION
ETC
DESCRIPTION
ETC
Page 31 of 45

Advertisement

Table of Contents
loading