0-10V Input Control Option Using Potentiometer And The On-Board 10Vdc Supply; 0-10V Input Control Option Using An External 0-10V Supply; Modbus Control Option; Figure 12 - Typical Wiring Diagram For Monitor & Control Operating Mode - Potentiometer Control Signal And On - Ebmpapst CN1116 Operating And Maintenance Instructions Manual

Modbus display & control (mdc)
Table of Contents

Advertisement

Operating and Maintenance Instructions

5.4.2.2 0-10V Input control option using potentiometer and the on-board 10VDC supply

Figure 12 - Typical wiring diagram for Monitor & Control operating mode – potentiometer control signal and on-

board 10VDC supply

5.4.2.2 0-10V Input control option using an external 0-10V supply

Figure 13 - Typical wiring diagram for Monitor & Control operating mode – external 0-10V control signal
CAUTION: Danger of damaging the fan if two power supplies are connected at the same time
Do not connect the fan's 10Vdc output to the controller if powering the controller from an external supply

5.4.3 Modbus control option

Figure 14 - Typical wiring diagram for Monitor & Control operating mode - Modbus RS485 control signal
CAUTION: Danger of damaging the fan if two power supplies are connected at the same time
Do not connect the fan's 10Vdc output to the controller if powering the controller from an external supply
210-OMI14229-Iss2