Unlike previous PCS offerings from IPWR, the Stabiliti™ Series PCS uses a novel Link
Transformer coupled with PPSA to deliver full galvanic isolation between the AC and DC power
ports. This isolation also delivers greater flexibility with regards to DC wiring options: floating;
grounded-unipolar; as well as bipolar battery types are all supported (minor wiring changes are
required to their DC power board connections).
All ports support bi-directional power flows (up to 30 kW max per port). Their highly flexible
operating modes are managed via Modbus RTU over an RS485 serial, control, and monitoring
interface. Modbus TCP is also supported. Future versions of the Stabiliti™ Series PCS will
support wireless connectivity options.

Unpacking and Inspecting the PCS

The Stabiliti is pallet shipped, and is enclosed in a purpose-built heavy-duty cardboard box.
Once unpacked, inspect the PCS for any obvious shipping damage. Immediately contact your
shipper and Ideal Power regarding any damage noted.

Mounting the PCS

The PCS, when installed on its wall mounting bracket weighs approximately 135 pounds.
External dimensions are 20.5" W x 40" H x 16" D. The PCS MUST always be installed in a
vertical upright position, this includes testing and evaluation purposes. Do not block cooling
airflow to the bottom air intake filter or the exhaust output, which is located on the upper door
face of the unit. Complete the mounting and installation following instructions in the Stabiliti™
Series Installations and Operations Manual (MAN-00115).

SECTION 3.0 LOW VOLTAGE WIRING

Wiring Access

The PCS wiring compartments are accessed by three screws which open the full-sized (20.5" x
40") hinged front door. All low-voltage wiring is directly terminated to connectors located on the
system's Control Board, located on the upper left side of the enclosure.
 Other than Ethernet and USB connections, low-voltage terminations are bare wire type.
Sourcing appropriate cables, conductors, and wiring are the customer's responsibility.
 Care should be taken when making up, routing, and connecting low-voltage cables. The
PCS should be disconnected from AC and DC power sources and a grounding strap
should be worn by the equipment installer. Refer to MAN-00115, Stabiliti™ Series
Installation and Operations Manual for additional information regarding low-voltage
wiring.
In all Stabiliti™ Series applications, an outside system controller is required to configure, control,
and monitor the PCS in real-time via the serial Modbus RTU, or Modbus TCP interface. These
energy storage systems may also utilize other low-voltage interfaces shown in Figure 1.