Ideal Power Stabiliti Series Quick Start Manual page 10

30 kw power conversion system (pcs)
Table of Contents

Advertisement

will eventually support a range of services at a particular Ethernet IP address, each service
accessed through one or more ports. Detailing all of these services is beyond the scope of
this preliminary Quick Start Guide.
NOTE: The 30C3 supports Modbus TCP on port 502, slave ID 255. Presently, two functions
are supported: Function 3, Read Holding Registers; and Function 6, Write Holding Register.
 Determining the Ethernet IP Address.
Once the PCS boots, it will request an IP address via DHCP (Dynamic Host Configuration
Protocol). Once an IP address is assigned by the local network, the PCS will display the
assigned IP address on its front panel display. If no IP address is assigned (e.g. if DHCP is
not available), the PCS will display 0.0.0.0 for the IP address (no address assigned). The
prototype PCS does not, presently, provide for retry of DHCP, so a power cycle of the PCS
is required if the 0.0.0.0 IP address is shown on the display. To ensure correct address
assignment, connect the network to the PCS prior to applying power to the unit's Control
Board.
NOTE: Static IP addresses are not supported. DHCP address assignment by the local network
is required. If DHCP is not available, communicate with the PCS via Modbus RTU.
 FTP (File Transfer Protocol)
Ideal Power use only. Supports remote file transfers to/from the PCS. This provides support
for collection of data and fault logs, and also for remote firmware updates. FTP uses ports
20 and 21.
Telnet
Ideal Power use only. Supports interactive application development, diagnostic
troubleshooting, and factory configuration. Telnet uses port 23.
#7 – USB Connector
Standard Mini-B USB connector.
NOTE: Not for customer use.
#8 - Aux 24 V Out
8-Pin Phoenix-style connector
 Pin 1 is Isolated 24 V return (ground)
 Pin 2 is Aux 24 V out
NOTE: Not for customer use.
#9 - Arc Fault Interface
8-Pin Phoenix-style connector.
Quick Start Guide Stabiliti™ Series PCS
MAN-00114, Rev D
Page 10 of 28