Table 4: Register Scaling Factors - Ideal Power Stabiliti Series Quick Start Manual

30 kw power conversion system (pcs)
Table of Contents

Advertisement

the Converter within the 16-bit range of 0-65535 for unsigned and -32768 to 32767 for signed
values.
These scaling factors apply to read only "measurement registers", as well as read/write "setpoint
registers" used to set desired output voltage, current, or power levels. The setpoint registers are
generally not utilized in 30C stand-alone applications.
Type
AC / DC Port
Voltage
DC Port Current
DC Port Power
AC Port Real
Power
AC Port Reactive
Power
AC Port Voltage
Ramp Rate
DC Port Current
Ramp Rate
AC/DC Port Power
Ramp Rate
Frequency
In 30C3 applications, a DC power command of +1500 on DC3 will deliver 15 kW of "export
power" (charging a battery). Conversely, a DC power command of -1000 on DC3 will deliver 10
kW of "import power" (discharging a battery).
The ramp rate command is a modifier of the power command defined above. It limits the port
ramp rate (power, current, or voltage depending on selected Control Method). A power ramp
rate setting of 300 limits the ramp up or ramp down of the commanded port to a 3 kW/second
rate.
Quick Start Guide Stabiliti™ Series PCS
MAN-00114, Rev D

Table 4: Register Scaling Factors

Scaling Factor
1 unit = 1.0 V
1 unit = 0.1 A
1 unit = 10 W
1 unit = 10 W
1 unit = 10 Var
1 unit = Volts per
second
1 unit = 0.1 A per
second
1 unit = 10 W per
second
1 unit = 0.001 Hz
Register
Actual Value
Read/Write
100
100 Vac / 100 Vdc
100
10.0 A
100
1000 W
100
1000 W
100
1000 Var (1 kVar)
100
100 V/second
100
10 A/second
100
1000 W/second
6000
60 Hz
Page 19 of 28