ICUBE™ Adaptive Defrost Module
Installation and Operation Manual
SAFETY SECTION
Risk of Fire or Electrical Shock
• Disconnect the power at the circuit breaker(s) or disconnect switch(es) before
installing or servicing.
• More than one circuit breaker or disconnect switch may be required to
de-energize the equipment before servicing.
• Installation and/or wiring must be in accordance with the national and local
electrical code requirements.
• Refer to DTAV40 or DDT40 for additional warnings and installation instructions.
See www.intermatic.com if needed.
• Only use the Intermatic supplied thermistor probe kit. The probe connection(s) to
the DTAV40 and DDT40 control are NOT an isolated Class 2 circuit. Use #18-14
AWG copper conductors for the field supplied wire to the thermistor probe.

PRODUCT DESCRIPTION

The ICUBE™ Adaptive Defrost Module, when added to an existing Grässlin™ DTAV40 - Defrost Control, provides the
DTAV40 Control with the ability to skip scheduled defrost events when they are not needed in order to save energy. Up to
four thermistor probes may be added to the control in order to monitor multiple evaporator coils. Thermistor probes may be
installed up to 400 ft (122 m) away from the ICUBE™ module at a remote dedicated or multiplex condensing unit (indoor or
outdoor) or within the freezer/cooler box. No changes to the installed defrost control terminal wiring (such as the wiring for
fans, defrost heater, or thermostat) is required.
To order additional thermistor probe kits (for example, to connect multiple evaporators to one control), use part number
178GR10K-1.
ICUBE™ Adaptive Defrost Module Contents – Part Number DDFM
The kit includes:
• One 10 ft (3.05 m) thermistor probe, with clip
• One 6 ft (1.83 m) input lead
• Four wire connectors
• One dead front
• One ICUBE™ Adaptive Defrost Module, DDFM
• Four #4-40 ¼" screws
WARNING
• Rotate the timer dial clockwise only, rotating counter-clockwise will damage the
timer.
• Do not move the clock hands on the timer. Moving the clock hands manually may
damage the timer.
• The thermistor wire may be extended up to 400 ft (122 m) using field-supplied
wiring between the DDT40 control and the thermistor probe location.
• This product is only intended to be used with Grässlin™ DTAV40 and DDT40
models.
All trademarks are the property of their respective owners.
FIG. 1
ICUBE™ Module Kit Contents
NOTICE

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ICUBE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Intermatic ICUBE

  • Page 1: Product Description

    Thermistor probes may be installed up to 400 ft (122 m) away from the ICUBE™ module at a remote dedicated or multiplex condensing unit (indoor or outdoor) or within the freezer/cooler box.
  • Page 2: Specifications

    FIG. 3, for example) or secured via a bracket inside the condensing unit control panel (as shown in FIG. 4, for example). The installation of the ICUBE™ module is the same for both instances. 4. If applicable, open the enclosure door.
  • Page 3 2. Orient the ICUBE™ module as shown in FIG. 5. 3. Install and fasten the ICUBE™ module to the control board with the screws provided. Be sure to align the FM Timer ICUBE™ module terminals with the terminal fasteners on the control board when placing. See FIG. 5.
  • Page 4 10. If additional thermistor probes are needed repeat all steps in this section. For large evaporators, additional thermistor probes may be added to a coil on each (opposite) side. 11. For multiple-evaporator installations, see "Optional: Multiple Evaporators" on page 6. ICUBE™ Adaptive Defrost Module...
  • Page 5: System Start-Up

    Dead Front 4. The control will sense the number of probes connected. Note: Observe the blue LED during startup in order to verify that the ICUBE™ module registers the correct FIG. 10 Attach the Provided Dead Front number of thermistor probes. The blue LED will flash once for each recognized probe.
  • Page 6 • Efficiency Mode – Scheduled defrosts are bypassed when the control is in this state. This is indicated when the blue LED is ON continuously. If there is no thermistor probe attached or a probe failure occurs, the ICUBE™ module operates solely off of the defrost timer and does not enter efficiency mode.
  • Page 7 Toutes les marques de commerce appartiennent à leurs nécessaire. propriétaires respectifs. • Utiliser uniquement la trousse de sonde à thermistance fournie par Intermatic. Les raccordements vers les panneaux de commande DTAV40 et DDT40 ne sont PAS des circuits isolés de catégorie 2. Utiliser des conducteurs en cuivre de 18 à...
  • Page 8: Caractéristiques

    Minuterie FM Minuterie FM Panneau de commande Panneau de commande Support FIG. 3 Retrait de la minuterie FM (modèle avec boîtier) FIG. 4 Retrait de la minuterie FM (Article DT-B en vente. Voir les instructions d’installation du DT-B.) Module de dégivrage adaptatif ICUBE...
  • Page 9 Module Remarque : Serrer doucement les vis. Ne pas trop serrer, ICUBE car cela pourrait provoquer un décapage. 4. Installer et fixer la minuterie FM au module ICUBE Panneau de commande avec les vis fournies. Veiller à aligner les bornes de la minuterie FM avec les attaches des bornes sur le...
  • Page 10 étapes de cette section. Pour les grands évaporateurs, il est possible d’ajouter des sondes à thermistance sur un serpentin de chaque côté (opposé). 11. Pour les installations à plusieurs évaporateurs, voir « En option : plusieurs évaporateurs », page 12. Module de dégivrage adaptatif ICUBE...
  • Page 11: Démarrage Du Système

    1. Au besoin, mettre à jour les heures de lancement et d’arrêt programmés. Voir les instructions pour le modèle DDT40 ou DTAV40, ou rendez-vous sur www.intermatic.com pour obtenir les instructions de programmation. 2. Remettre en place le couvercle de l’écran isolant fourni, le cas échéant.
  • Page 12 Cela correspond à la DEL bleue allumée en permanence. Si aucune sonde à thermistance n’a été fixée ou en cas de panne de la sonde, le module ICUBE fonctionne uniquement à partir de la minuterie de dégivrage et ne passe pas en mode économique.
  • Page 13: Descripción Del Producto

    Las sondas de termistor se pueden instalar hasta 122 m (400 pies) del módulo ICUBE™ en una unidad de condensación remota dedicada o múltiple (para interior o exterior) o dentro de la caja del congelador/refrigerador. No es necesario realizar cambios al cableado del terminal de control de descongelación instalado (como el cableado para los ventiladores, calefactor de descongelación o termostato).
  • Page 14: Especificaciones

    FIG. 3, por ejemplo) o se puede fijar en un soporte adentro del panel de control de la unidad de condensación (como se muestra en la FIG. 4, por ejemplo). La instalación del módulo ICUBE™ es la misma en ambos casos. FIG. 2 Frente muerto actual 4.
  • Page 15 2. Oriente el módulo ICUBE™ como se muestra en la FIG. 3. Instale y asegure el módulo ICUBE™ al panel de Temporizador FM control con los tornillos incluidos. Cuando lo instale, debe alinear los terminales del módulo ICUBE™ Tornillo con los fiadores de terminales del panel de control.
  • Page 16 Para evaporadores de gran tamaño, puede agregar sondas de termistor adicionales a un serpentín a cada lado (opuesto). 11. Para instalaciones con varios evaporadores, consulte "Opcional: Varios evaporadores" en la página 18. ICUBE™ Adaptive Defrost Module...
  • Page 17: Arranque Del Sistema

    4. El control detectará la cantidad de sondas conectadas.  Nota: Observe la luz LED azul durante el arranque para verificar que el módulo ICUBE™ registra la cantidad FIG. 10 Colocar el frente muerto incluido correcta de sondas de termistor. La luz LED azul destellará...
  • Page 18 LED encendida de forma continua. Si no hay una sonda de termistor adjunta o se produce un error de la sonda, el módulo ICUBE™ funciona únicamente fuera del temporizador de descongelación y no entra en el modo de eficiencia.

Table of Contents