¢ Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.
1)
11
2)
20
3)
22
4)
30/31
5)
40
6)
42
7)
44
8)
46
9)
48
10)
92/93
11)
95
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
11
2) Ceiling height
Select the appropriate ceiling height according to the place of installation.
Function number
20
For the specific height for each setting value, refer to "Installation space" in Chapter 2.
on page 4.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet
mode.
9,000 Btu/h models cannot be installed in high ceilings. Do not change this setting.
3) Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function number
22
10-2. Function settings by using remote controller
Filter sign
Ceiling height
Outlet directions
Room temperature control for indoor unit sensor
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Room temperature control for wired remote controller sensor
Heat insulation condition (building insulation)
Setting value
00
01
02
03
Setting value
00
01
Setting value
00
01
Functions
Setting description
Standard (2,500 hours)
Long interval (4,400 hours)
Short interval (1,250 hours)
No indication
Setting description
Standard
High ceiling
Setting description
4-way
3-way
- 36 -
Factory setting
♦
Factory setting
♦
"Dimensions"
Factory setting
♦
10. Function settings