Fresh-Air Control Output - Fujitsu AUU9RLF Design & Technical Manual

Cassette type
Hide thumbs Also See for AUU9RLF:
Table of Contents

Advertisement

8-3. Fresh-air control output

Signal linked to the indoor unit fan on can be output.
NOTE: In cold-air prevention control operation, the signal becomes off.
 Circuit diagram example
12 V
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Relay spec: Rated DC 12 V, 50 mA or less.
Indoor unit
Output signal
 Optional part
NOTE: This wire is included in both Fresh air intake kit.
8-3. Fresh-air control output
Indoor unit
control PCB
Connector
1
On/Off
2
33 ft.*
(10 m)
Operation
Stop
On
Off
Model name
UTZ-VXAA
Connected unit
Example: Relay unit
Signal
Locally purchased
- 29 -
Example: Fan
Relay
power
supply
Exterior
Fresh-air output wire
8. External input and output

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Auu18rlfAuu12rlfAou18rlfcAou9rlfcAou12rlfc

Table of Contents