5.5.4. Standard fittings for withdrawable circuit-breakers
The basic versions of the withdrawable circuit-breakers are
three-pole and provided with:
– EL type manual operating mechanism
– Mechanical signalling device for closing spring charged/dis -
charged
– Mechanical signalling device for circuit-breaker open/closed
– Closing pushbutton
– Opening pushbutton
– Operation counter
– Set of ten circuit-breaker open/closed auxiliary contacts
Note: with the set of ten auxiliary contacts supplied as standard and
the maximum electrical accessories, three break contacts are available
(signalling circuit-breaker open) and four make contacts (signalling circuit-
breaker closed).
– Lever for manual charging of the closing spring incorporated
in the operating mechanism
– Isolating contacts
– Racking-out/racking-in lever (the quantity must be
established according to the number of pieces of apparatus
ordered).
5.6.

Characteristics of the electrical accessories

– Shunt opening release (-MO1)
– Additional shunt opening release (-MO2)
– Shunt closing release (-MC)
– Locking magnet on the actuator (-RL1)
Un
24 - 30 - 48 - 60 - 110 - 125 - 220 - 250 V–
Un
48 - 60 - 110 - 120 - 127 - 220 ... 240 V~ 50 Hz
Un
110 - 120 - 127 - 220 - 240 V~ 60 Hz
Operating limits
70 ... 110 % Un
Inrush power (Ps)
DC 200 W; AC = 200 VA
Inrush time
approx. 100 ms
Continuous power (Pc)
DC = 5 W; AC = 5 VA
Opening time
35 ... 60 ms
Closing time
30 ... 80 ms
Insulation voltage
2000 V 50 Hz (for 1 min)
Undervoltage release (-MU)
Un
24 - 30 - 48 - 60 - 110 - 125 - 220 - 250 V–
Un
48 - 60 - 110 - 120 - 127 - 220 ... 240 V~ 50 Hz
Un
110 - 120 ... 127 - 220 ... 240 V~ 60 Hz
Operating limits
– circuit-breaker opening 35-70% Un
– circuit-breaker closing 85-110% Un
Inrush power (Ps)
DC 200 W; AC = 200 VA
Inrush time
approx. 100 ms
Continuous power
DC = 5 W; AC = 5 VA
Opening time
30 ms
Insulation voltage
2000 V 50 Hz (for 1 min)
Electronic time delay device for undervoltage release
(mounted outside the circuit-breaker)
Un
24 ... 30 - 48 - 60 - 110 ... 127 - 220 ... 250 V–
Un
48 - 60 - 110 ... 127 - 220 ... 240 V~ 50/60 Hz
Adjustable opening time
(release + time delay
0.5-1-1.5-2-3 s
device)