5.5.1. General characteristics of withdrawable circuit-breakers
General characteristics of withdrawable circuit-breakers
for UniGear ZS2 & PowerCube modules (36 kV)
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity
(rated short-circuit breaking current symmetrical)
Rated short-time withstand current (3s)
Making capacity
Operation sequence
Opening time
Arcing time
Total breaking time
Closing time
P P
Maximum
overall
H
dimensions
W
Weight
Operating temperature
Tropicalization
Electromagnetic compatibility
Note: * - To be released. Contact ABB
IEC 62271-100 •
VDE 0671; CEI 17-1 (File 1375) •
Ur [kV] 36
Us [kV] 36
Ud (1 min) [kV]
Up [kV] 170
fr [Hz] 50-60
Isc [kA]
Ik [kA]
Ip [kA]
[ O - 0.3 s - CO - 3 min - CO ]
H [mm]
W [mm]
D [mm]
Pole distance P [mm]
D
IEC: 60068-2-30, 60721-2-1 •
IEC: 62271-1 •
VD4/W 36
70
Ir [A]
1250
1600
2000
2500*
--
--
--
--
31.5
31.5
31.5
31.5
--
--
--
--
--
--
--
--
31.5
31.5
31.5
31.5
--
--
--
--
--
--
--
--
80
80
80
80
--
--
--
--
[ms] 33 ... 60
[ms] 10 ... 15
[ms] 43 ... 75
[ms] 60 ... 80
973
973
973
973
842
842
842
842
788
788
788
788
275
275
275
275
230
245
275
[kg]
[°C] - 5 ... + 40
-
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vd4 seriesVd4/w 36

Table of Contents