Mitsubishi SRK25ZSP-W Service Manual page 30

Inverter wall mounted type residential air-conditioners (split system, air to air heat pump type)
Hide thumbs Also See for SRK25ZSP-W:
Table of Contents

Advertisement

Current cut
-
Current safe stop
Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor unit PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
.
unit
unit
unit
SRC25, 35 : 4.428Ω (U-V, V-W, U-W) or more at 20ºC
SRC45 : 1.728Ω (U-V) , 1.705Ω (V-W) , 1.761Ω (U-W) or more at 20ºC
unit
28
-
-
*  
33.
Overload operation, compressor
lock, overcharge
'09•SRK-DB-087D
'18 • SRK-SM-259
35.