Mollet LF20 Instruction

Yo-yo sensing level measurement continuous level indication for bulk solids
Hide thumbs Also See for LF20:

Advertisement

M LLET
Füllstandtechnik
Yo-Yo sensing level measurement
continuous level indication for bulk solids
Instruction for parameterisation
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846
S/N serial number
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameterisation
LF
silo number / silo name
Page
. . . . . .
02/14
LF-PA-01
©
by MOLLET
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LF20 and is the answer not in the manual?

Questions and answers

Summary of Contents for Mollet LF20

  • Page 1: Table Of Contents

    ..............MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846...
  • Page 2: Display And Input Keys | Key Functions | Menu Levels | Numerical Entry And Text Input

    6. Pressing both keys at the same time interrupts insert procedure. The edit mode is left. LF-PA-02 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 3: Lf20 First Switch-On | Hardware Locking Mechanism

    @ -symbol is shown unlock$parameter$074 @$hardware$locking Inputs no more possible. measured$value$$$000 Measuring procedures can take place. $$$$$63.42 % ~~~~~~~~~~~_________ Deblock parameterisation pressing at the same time MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-03 © by MOLLET...
  • Page 4: Lf20 Parameterise

    - select „bolting“ for input 1 [010] or 2 [012] and wire the signal PG 08& input accordingly group$selection$$08& page LF-PA-22 (see page LF-PA06) µsystem$parameters~~ group$selection$$0D& Complex measurement tasks require further settings. $service$$$$$$$$$20 LF-PA-04 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 5: Basic Setup

    - Start by pressing start-key at LF20 LF-PA-06 - Start by signal input 1 [010] or 2 [012] Periodical - Start by time control of the LF20 depending on LF-PA-11 time interval in P [021] and time unit in P [022] Manual - Measurement cycles can be started with man.
  • Page 6: Signal Inputs

    LF-GI-08 Parameter Function of input 1 or 2 bolting If there is a signal at the input, the LF20 is blocked for further measurements. A running measurement is cancelled immediately. The sensing weight is moved into the upper limit position.
  • Page 7: Relay Output 1 And

    (end of measurement). page LF-PA-04 measuring during the entire measuring period. MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-07 © by MOLLET...
  • Page 8: Relay Output 3 And 4

    (end of measurement). measuring during the entire measuring period. LF-PA-08 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 9: Relay Output - Pulse Settings - Reset Pulse

    300 ms Default value length$of$the ____________ ms reset$pulse 30 ms ... 1000 ms Range of values P 01A, return or option page LF-PA-07 MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-09 © by MOLLET...
  • Page 10: Measurement Parameters

    Range of values $$$$$$$5678 The counter shows the number of measurement cycles. Reset counter to 0 after maintenance was executed. P 026 page LF-PA-13 LF-PA-10 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 11: Measurement Parameters

    The use of the relay output function counter pulse [015/016] makes no sense, as the sensing weight does not approach a defined point at the end of the measurement. (and therefore no defined distance) MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-11 ©...
  • Page 12: Manual Mode

    If the height of the silo is not exactly known, the empty calibration [001] could be determined with the help of the manual mode. empty Minimum filling level 022-0603 LF-PA-12 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 13: Simulation

    µm3~~~~~~~~~~~~~~~~~ max.$scale$$$$$$$057 $$$$$$$$1000 m3 sim.$value$$$$$$$027 simulation$$$$$$$026 µsim.$Volume~~~~~~~~ $$$$$$200 m3 Current output present$error simulation measured$value$$$000 activated $ß $$$$$$$$$$$$$$$$W621 7,1 mA $$$$200.00 m3 $$$$$$$$$$$$$$$$W621 ~~~~~~~~~~~~~~~~____ MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-13 © by MOLLET...
  • Page 14: Current Output

    The setting residual volume m/ft/in or residual volume TE cause a declining output current when the fill level rises. [mA] Residual volume Residual volume LF-PA-14 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 15: Output On Alarm

    041 output on alarm output$on$alarm $$041 $$$$$$$3.60 mA 3,60 mA Default value ___________ mA Range of values 0 ... 22,00 mA P 042 page LF-PA-16 MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-15 © by MOLLET...
  • Page 16: Safety Distance

    Full calibration [003] ./. Safety distance [042] = Measured value (fill level) - Current output represents the measured value. - Warning [W661] is shown and ß is blinking. LF-PA-16 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 17: Security Distance

    $warning ‘ alarm This parameter determine the device reaction, in case the sensing weight reaches the security distance [043]. $$$Return$to $$$group$selection page LF-PA-04 MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-17 © by MOLLET...
  • Page 18: Linearisation

    In the dimension unit selected and the number of decimal $$$$$100,00$% places selected. ___________ [056] Default value 1 ... 100000 Range of values $$$Return$to $$$group$selection page LF-PA-04 LF-PA-18 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 19: Display

    All points on the display are activated for around two µoff~~~~~~~~~~~~~~~~ ~~~~~~~~~~~~~~~~~~~~ seconds. ~~~~~~~~~~~~~~~~~~~~ ~~~~~~~~~~~~~~~~~~~~ Default value Switches automatically to „off“ after this 2 seconds. $$$Return$to $$$group$selection page LF-PA-04 MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-19 © by MOLLET...
  • Page 20: Diagnostics

    100 (unlocks parameter entry) Default value see manual ___________________ < > 100 (locks parameter entry) Range of values Note unlock parameter. $$$Return$to $$$group$selection page LF-PA-04 LF-PA-20 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...
  • Page 21: Error Messages

    W661 W681 Measurement range exceeded W700 Tape / rope change required - Check measuring tape and replace if necessary - Reset maintenance interval counter MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Parameterisation 02/14 LF-PA-21 © by MOLLET...
  • Page 22: System Parameters

    ‘ exception of the customer unit (CU), in case this has been ‘ selected. ‘ m (meter) Default value $$$Return$to $$$group$selection page LF-PA-04 LF-PA-22 02/14 Parameterisation MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 © by MOLLET...

Table of Contents