Output Network Variables (Nvo's) Description - Viconics PIR Ready7 VT76x7 Series Integration Manual

Programmable & non-programmable thermostats for commercial hvac applications; for lonworks
Table of Contents

Advertisement

Output Network Variables (nvo's) Description

All output network variables will be updated no faster than the Minimum Send Time (nciMinOutTm)
configuration value, if used.
An output network variable will be transmitted immediately when its value has changed significantly.
Additionally, this variable will also be transmitted as a heartbeat output on a regular basis as dictated by the
Maximum Send Time (nciSndHrtBt) configuration value.
Parameter
Variable Name
Room
network output
Temperature
SNVT_temp_p
nvoSpaceTemp
Unit Status
network output
SNVT_hvac_status
nvoUnitStatus
Outdoor
network output
Temperature
SNVT_temp_p
nvoOutdoorTemp
Function
This output network variable is used to monitor the effective
space temperature sensor that the Space Comfort Controller is
using for control. This output echoes the value of the input.
Valid Range: -40 to 122°F (-40 to 50°C)
The value 621.07°F (327.67°C or 0x7FFF) will be sent as an
invalid value in case of a sensor failure.
This output network variable is available to report the Space
Comfort Controller status. It combines the operating mode, the
capacity of heating and cooling used and an indication if any
alarms are present in the object.
Sub
Name
Valid Value
01
mode
HVAC_HEAT
HVAC_MRNG_WRMUP – Not Used
HVAC_COOL
HVAC_NIGHT_PURGE – Not Used
HVAC_PRE_COOL – Not Used
HVAC_HVAC_OFF
HVAC_HVAC_TEST – Not Used
HVAC_HVAC_EMERG_HEAT – Not Used
HVAC_FAN_ONLY – Not Used
HVAC_MAX_HEAT – Not Used
02:
heat_output_
0-100%
primary
03
heat_output_
Not Used
secondary
04
cool_output:
0-100%
05
econ_output
Not Used
06
fan_output
0-100%
07
In_alarm
0 (No alarms)
1 (Alarm On)
0x7FF (Alarming disabled) – Not Used
This output network variable is used to monitor the outdoor air
temperature.
Valid Range: -40 to 122°F (-40 to 50°C)
The value 621.07°F (327.67°C or 0x7FFF) will be sent as an
invalid value in case of a sensor failure or if unconnected.