Configuration properties (nci's) Description

Parameter
Variable Name
Schedule
network input config
UNVT_day_sched
nciDay_Sched[x]
x = 0 to 6
Temperature
network input config
Setpoints
SNVT_temp_setpt
nciSetPts
Thermostat's
UNVT_cfg_1_rtu_hp
common
nciCfg1RtuHp
configuration
parameters
network input
config
Function
This configuration property defines the schedule for every day of
the week (from Monday to Sunday or from day 0 to day 6). This
nci is linked with the nvoEffectOccup variable.
2 or 4 events can entered depending on the nb_of_events
variable.
Starting and ending time are entered in minutes, e.i. 11:59 pm is
equal to 1439 minutes (23 hours * 60 min + 59 min)
Valid Range : 0 to 1439 minutes
Default values:
Sub
Name
1
occupied_event_1
2
unoccupied_event_2
3
occupied_event_3
4
unoccupied_event_4
This configuration property defines the space temperature
setpoints for various heat, cool and occupancy modes.
The stand-by setpoints can be modified but are not used by the
controller, as it does not support Stand-By occupancy mode.
Valid Range and Default values:
Sub
Name
01
occupied_cool
02
standby_cool
03
unoccupied_cool
04
occupied_heat
05
standby_heat
06
unoccupied_heat
This configuration property defines the thermostat's common
configuration parameters and their settings.
Valid Range and Default values:
Name
Valid Range
password
0 to 1000
unoccupied timer
0.5 to 24.0 hours
anticycle
0, 1, 2, 3, 4, or 5
minutes
power-up delay
10 to 120 sec.
temporary occ time
0, 1, 2, 3 to 12 hours
heating stages cph
3, 4, 5, 6, 7 or 8 CPH
cooling stages cph
3 or 4 CPH
heat maximum
40 to 90°F (4.5 to 32°C)
setpoint
cool minimum
54 to 100°F
setpoint
(12 to 37.5°C)
oa temp heat lockout -15 to 120°F (-26 to
49°C)
oa temp cool
-40 to 95°F (-40 to
lockout
35°C)
calib room sensor
±5°F (±2.5°C)
calib outdoor air
±5°F (±2.5°C)
sensor
deadband
2 to 4°F with 1°F
increments (1 to 2°C)
Default Value
0
1439
0
1439
Valid Range
Default value
54 to 100°F
73.5°F (23°C)
(12 to 37.5°C)
Not Used
Not Used
54 to 100°F
82.5°F (28°C)
(12 to 37.5°C)
40 to 90°F
70°F (21°C)
(4.5 to 32°C)
Not Used
Not Used
40 to 90°F
61°F (16°C)
(4.5 to 32°C)
Default value
0
0.5
2 minutes
10 sec.
3 hours
4 CPH
4 CPH
90°F
54°F
120°F
-40°F
0°F
0°F
2°F
12