Download Print this page

Honeywell CN05 Series Manual page 5

Non-spring return direct-coupled damper actuators for floating and two-position control

Advertisement

Fig. 8.
CN6105/CN6110 (2-position mode)
L
> 3 mm!
230V ~
Fig. 9.
CN4605/CN4610 (2-position mode)
Fig. 10. End switches
NOTE: Both internal end switches must be connected to the
same power source.
CN05,CN10 SERIES DAMPER ACTUATORS FOR FLOATING/2-POSITON CONTROL
1
230V~
2
CW
3
CCW
N
4
5
Tables 3,4 and 5 summarize the information presented in the
preceding wiring diagrams.
Table 3. Signals at terminals for CN6105/CN6110
ter-
signal in floating
minal
2
common ~/-
24 V ~/+
3
(control signal)
24 V ~/+
4
(control signal)
NOTE: All cables connected to these terminals must be
equipped with spark suppression.
Table 4. Signals at terminals for CN4605/CN4610
terminal
1
2
3
NOTE: All cables connected to these terminals must be
equipped with spark suppression.
Table 5. Internal end switches (SSW2)
terminal
S1
common lead for switches A and B
change-over switch A (S1/S2 opens and
S1/S3 closes when shaft adapter moves CW
S2 / S3
past 5°; reverts to original state when shaft
adapter moves CCW past 5°).
change-over switch B (S1/S5 opens and
S1/S6 closes when shaft adapter moves CW
S5 / S6
past 85°; reverts to original state when shaft
adapter moves CCW past 85°).
5
signal in 2-pos. mode
common ~/-
24 V ~/+
(control/ power signal)
24 V ~/+
(control signal/power)
signal
L (230 V ~)
N (230 V ~)
control signal
type of switch
CN0B-0544CH33 R0805B

Advertisement

loading

This manual is also suitable for:

Cn10 series