Technical data
(modified 96-11)
Energizing inputs
Phase and neutral current inputs, terminals
Rated current I
n
Thermal withstand capability
- continuously
- for 1 s
Dynamic current withstand, half-wave value
Input impedance
Phase current monitoring range
Phase unbalance current monitoring range
Rated frequency
Output contact ratings
Reconnection enable and trip contact
Terminals
- Rated voltage
- Carry continuously
- Make and carry for 0.5 s
- Make and carry for 3.0 s
- Breaking capacity for dc, when the control
circuit time-constant L/R < 40ms,
at 48/110/220 V dc control circuit voltage
Contact material
Start and signalling contacts
Terminals
- Rated voltage
- Carry continuously
- Make and carry for 0.5 s
- Make and carry for 3.0 s
- Breaking capacity for dc, when the control
circuit time-constant L/R < 40ms,
at 48/110/220 V dc control circuit voltage
Contact material
External control inputs
Blocking and command inputs
External control voltage level
Typical control current of input circuit
Power supply and output relay module
Supply and relay module, type SPTU 240 R2
Supply and relay module, type SPTU 48 R2
Power consumption under quiescent/operating
conditions
1-3, 4-6, 7-9, 25-27
1-2, 4-5, 7-8, 25-26
1 A
5 A
4 A
20 A
100 A
500 A
250 A
750 A
< 100 mΩ
< 20 mΩ
0...8.5 x I
n
0...212% ∆I
n
50/60 Hz
65-66, 74-75
250 V dc/ac
5 A
30 A
15 A
5 A / 3 A / 1 A
AgCdO
2
70-71-72, 68-69, 77-78, 80-81
250 V dc/ac
5 A
10 A
8 A
1A / 0.25A / 0.15A
AgCdO
2
10-11
18...265 V dc or 80...265 V ac
2 mA
80...265 V dc/ac
18...80 V dc (on request)
4 W / 6 W
15