ABB SPAJ 160 C User Manual And Technical Description page 17

Capacitor protection relay
Table of Contents

Advertisement

Data transmission
Transmission mode
Data code
Data transfer rate, selectable
Electrical/optical bus connection module
powered from the host relay
- for plastic core cables
- for glass fibre cables
Electrical/optical bus connection module
powered from the host relay or an external
power source
- for plastic core cables
- for glass fibre cables
Test voltages *)
Dielectric test voltage according to IEC 255-5
Impulse test voltage according to IEC 255-5
Insulation resistance according to IEC 255-5
Disturbance tests *)
High-frequency (1MHz) disturbance test
according to IEC 255-22-1, class III
- common mode
- differential mode
Fast transients according to IEC 255-22-4,
class III and IEC 801-4, level 4
- power supply inputs
- other inputs
Electrostatic discharge test according to
IEC 255-22-2 and IEC 801-2, class III
- air discharge
- contact discharge
Environmental conditions
Specified ambient service temperature range
Temperature influence on the operating values
of the relay over the specified ambient service
temperature range
Long term damp heat withstand according
to IEC 68-2-3
Transport and storage temperature range
Degree of protecting by enclosure of the relay case
as per IEC 529 when panel mounted
Mass of the relay
*) The insulation and disturbance tests do not apply to the serial port, which is used for the bus
connection module only.
Fibre optic serial bus
ASCII
4800 Bd or 9600 Bd
SPA-ZC 21 BB
SPA-ZC 21 MM
SPA-ZC 17 BB
SPA-ZC 17 MM
2.0 kV, 50 Hz, 1 min
5 kV, 1.2/50 µs, 0.5 J
>100 MΩ, 500 V dc
2.5 kV
1.0 kV
4 kV, 5/50 ns
2 kV, 5/50 ns
8 kV
6 kV
o
-10 ... +55
C
o
< 0.2 %/
C
o
< 95 % at 40
C for 56 d/a
o
-40 ... +70
C
IP 54
3.5 kg
17