Power Supply And Output Relay Module; Technical Data (Modified 2002-04) - ABB SPAJ 140 C User Manual And Technical Description

Combined overcurrent and earth-fault relay
Table of Contents

Advertisement

Technical data
(modified 2002-04)
10
Energizing inputs
Rated current I
n
Thermal withstand capability
- continuously
- for 1 s
Dynamic current withstand, half-wave value
Input impedance
Rated frequency f
, on request
n
Output contact ratings
Tripping contacts
Terminals
Rated voltage
Continuous carry
Make and carry for 0.5 s
Make and carry for 3.0 s
Breaking capacity for dc, when the trip circuit
time-constant L/R ≤ 40 ms, at 48/110/220 V dc
Signalling contacts
Terminals
Rated voltage
Continuous carry
Make and carry for 0.5 s
Make and carry for 3.0 s
Breaking capacity for dc, when the signal circuit
time-constant L/R ≤ 40 ms, at 48/110/220 V dc
signal circuit voltage
External control inputs
Blocking, remote reset or remote setting input
Control voltage level
Control current of activated input

Power supply and output relay module

Supply and output relay module, type SPTU 240 R1
Supply and output relay module, type SPTU 48 R1
Power consumption under quiescent/operating
conditions
1 A
5 A
4 A
20 A
100 A
500 A
250 A
1250 A
<100 mΩ
<20 mΩ
50 Hz or 60 Hz
65-66, 74-75
250 V dc/ac
5 A
30 A
15 A
5 A/3 A/1 A
70-71-72, 68-69, 77-78, 80-81
250 V dc/ac
5 A
10 A
8 A
1 A/0.25 A/0.15 A
10-11
18...265 V dc or 80...265 V ac
2...20 mA
80...265 V dc/ac
18...80 V dc
~4 W/ ~6 W