NVF5 Series User Manual
Figure 6-3-3 Speed Tracking and then Start Time Sequence Chart
6.3.2 Stop Mode
The NVF5 has three kinds of stop modes,ramp deceleration stop、coast stop、ramp
stop+DC injection braking stop.Set parameter F1.05 to select stop mode.
Code
Stop Mode
F1.05
DC braking
F1.06
Starting frequency
DC braking
F1.07
wait time
DC braking
F1.08
current
DC braking time
F1.09
Ramp Decel. Stop
Set parameter F1.05=0,the inverter ramp decel. Stop.When the stop command is
effective,the inverter will ramp deceleration stop ,when the frequency decelerate to 0 ,the
inverter stop.
Outmut
freq.
Motor speed
Motor speed tracking
Name
Chapter 6 Parameter Function Description
Acceleration
time
Default
Setting Range
0 ~ 2
0
0.00Hz ~ F0.07
0.00Hz
(0.0 ~ 100.0)s
0.0s
(0.0 ~ 100.0) %
0.0%
0.0s
(0.0 ~ 100.0)s
- 59 -
Time
Description
Decel. Ramp
0:
Stop
Coast Stop
1:
Ramp
2:
Stop+DC
Injection Brake
--
--
100%(Inverter
Rated Current)
--
Need help?