Ariston CLAS HE R Installation And Servicing Instructions page 33

Condensing wall-hung gas boiler
Table of Contents

Advertisement

menu 2 - Boiler parameters
NOTE: To access the menus, see page 36
submenu 3 - parameter 1
Maximum Heating Power adjustment
submenu 2 - parameter 0
Soft light Ignition
submenu 3 - parameter 5
Heating ignition delay
Maximum Heating Power adjustment
The maximum heating power can be adjusted to between the
maximum power allowed by the boiler and the minimum power.
The display shows the value between 100% ("99" on the display) and
0% ("0").
To check the maximum heating power, access menu 2/sub menu 3/
parameter 1, check the value and, if necessary, modify it as indicated
in the Gas Regulation table. (below).
Checking slow ignition power
The soft light can be adjusted between the maximum power (shown
on the display as "99", i.e. 100%) and the minimum power (shown on
the display as "1", i.e. 1%).
To check the slow ignition power, access menu 2/sub menu 2/
parameter 0.
Heating ignition delay adjustment
This parameter – menu 2/sub menu 3/parameter 5 - can be used
to manually (0) or automatically (1) set the delay time before the
subsequent reignition of the burner after it has switched off on
reaching the desired temperature in central heating mode.
By selecting manual (0), it is possible to set the delay in minutes
using the successive parameter (menu 2/sub menu 3/parameter 6),
to a time between 0 and 7 minutes.
Automatic selection means that the boiler will establish the delay
time based on the set-point temperature.
Gas setting
lower Wobbe index
(15°C, 1013 mbar) (MJ/m3)
slow ignition
minimum fan speed(%)
maximum output fan speed (%)
gas valve restrictor(ø)
gas flow max/min
(15°C, 1013 mbar)
max C.H.
(nat - m3/h)
min
(GPL - kg/h)
CLAS HE R
24 EU
parameters
G20
G31
45,67
70,69
220
60
233
16
234
85
NO
3,80
2,33
1,71
0,58
0,43
COMMISSIONING
38
35
30
24
24
/
33