Binary inputs (objects 1 and 2) are supported as defined by the previous table. Binary inputs 0
599 and 1200
1223 are scanned approximately once per second to generate events. When time
–
is reported with these event objects, it is the time at which the scanner observed the bit change.
This may be significantly delayed from when the original source changed and should not be used
for sequence-of-events determination.
In order to determine an element's point index, consult the Relay Word Bits table in Section 9:
Setting the Relay. Locate the element in question in the table and note the Relay Word row
number. From that row number, subtract the row number of the first Relay Word row (usually 2)
and multiply that result by 8. This is the index of the right-most element of the Relay Word row
of the element in question. Count over to the original element and add that to get the point
index. Binary Inputs 600
carry the time stamp of actual occurrence. Static reads from these inputs will show the same
data as a read from the corresponding index in the 0
the SER list (SET R) will generate events in the 600
Analog Inputs (objects 30 and 32) are supported as defined by the preceding table. The values
are reported in primary units. Analog inputs 28
scaled according to the DECPLM setting (e.g., if DECPLM is 3, then the value is multiplied by
1000). Analog inputs 58
(current magnitudes) are scaled according to the DECPLA setting. The even-numbered points in
8
15 and 22
27 (voltage magnitudes) are scaled according to the DECPLV setting. Analog
–
–
inputs 36
41, 106, and the odd-numbered points in 0
–
100. The remaining analogs are not scaled.
Event-class messages are generated whenever an input changes beyond the value given by the
ANADB setting. The dead-band check is done after any scaling is applied. The angles (the odd
numbered points in 0
band check, the corresponding magnitude (the preceding point) contains a value greater than the
value given by the ANADB setting. Analog inputs are scanned at approximately a 1-second rate,
except for analogs 103
initiated. Analogs 103
fault and do not generate event messages. Analog 103 is a 16-bit composite value, where the
upper byte is defined as follows:
Value
1
2
4
8
And the lower byte is defined as follows:
Value
0
1
2
4
8
H-12
1199 are derived from the Sequential Events Recorder (SER) and
–
62, 79
83, and the even-numbered points in 0
–
–
27 and 113
147) will only generate an event if, in addition to their dead-
–
–
111. During a scan, all events generated will use the time the scan was
–
111 are derived from the history queue data for the most recently read
–
Event Cause
Trigger command
Pulse command
Trip element
ER element
Fault Type
Indeterminate
A-Phase
B-Phase
C-Phase
Ground
Distributed Network Protocol (DNP) 3.00 Level 2
SEL-311L Instruction Manual
599 group. Only points that are actually in
–
1199 group.
–
35, 42
57, 63
78, 84
–
–
–
–
27 and 113
147 (angles) are scaled by
–
–
–
102, and 104 are further
7, 16
21, and 112
146
–
–
–
Date Code 20010625
Need help?
Do you have a question about the SEL-311L and is the answer not in the manual?