266
FIO_11_AO_slot1
(10090)
Illustration
Execution time
Operation
Standard function blocks
FIO_11_AO_slot1
TLA1 1 msec
AO Min
AO Max
AO Min Scale
AO Max Scale
AO scaled
4.9 µs
The block controls the analogue output (AO1) of a FIO-11 Analog I/O Extension
mounted on slot 1 of the drive control unit.
The block converts the input signal (AO scaled) to a 0...20 mA signal (AO) that drives
the analogue output; the input range AO Min Scale ... AO Max Scale corresponds to
the current signal range of AO Min ... AO Max.
AO Min Scale must be smaller than AO Max Scale; AO Max can be greater or smaller
than AO Min.
AO Min < AO Max
53
(1)
AO(53)
AO
Error(53)
Error
AO [mA]
20
AO Max
0
-32768
0
AO Min
32768
AO scaled