Siemens SIMATIC S7 300 PLC Getting Started page 63

Controlling a sinamics s120
Hide thumbs Also See for SIMATIC S7 300 PLC:
Table of Contents

Advertisement

Sequence
Activity
39
Select parameter "p210" and enter "345".
The smart line module and the motor module of the SINAMICS S120 training case have been especially
equipped for operation on a 230 V system. For this reason, "Parameter p210" of the connected drives must
be set to the following value, which differs from the factory settings:
p210 = 345 V device connection voltage SERVO/VECTOR
The setting of "parameter p210 = 345 V" cannot be calculated by the SINAMICS operating system and is
pre-assigned for the error-free operation of the SINAMICS S120 training case on the 230 V system.
40
In the project navigator, open the tree structure SIMATIC 300(1) > Technology > SINAMICS_S120 >
Configuration. Double-click "Configuration" to start the SINAMICS
CPU 317T-2 DP: Controlling a SINAMICS S120
Getting Started, 12/2005, A5E00480391-01
3.9 9. Step: Configuration of the SINAMICS drive with S7T Config
Result
configuration.
®
Learning units
3-53