5. MALFUNCTION

Table 5-1
No.
Error code
1
E0
Outdoor unit communication error
2
E1
Phase error
3
E2
Communication error with indoor unit
4
E4
Outdoor temp. sensor error
5
E5
Voltage protection
6
E7
Discharge sensor error
7
E8
Outdoor unit address error
8
xE9
S11 setting does not match the capacity
9
xH0
Communication error between DSP and main chip
10
H1
Communication error between 0537 and main chip
11
H2
Qty. of outdoor units decreases error
H3
Qty. of outdoor units increases error
12
13
xH4
P6 protection has been activated 3 times in 60 minutes
14
H5
P2 protection has been activated 3 times in 60 minutes.
15
H6
P4 protection has been activated 3 times in 100 minutes.
16
H7
Qty. of indoor units not recognised
17
H8
High pressure sensor error
18
H9
P9 protection has been activated 3 times in 60 minutes
19
C7
PL protection has been activated 3 times in 100 minutes.
20
xHd
Auxiliary unit error (X=1,2,3, e.g, 1Hd stands for auxiliary unit1 error)
21
P0
Inverter compressor maximum temp. protection
22
P1
High pressure protection
23
P2
Low pressure protection
24
xP3
Compressor current protection
25
P4
Discharge temp. protection
26
P5
High condenser temp. protection
x (P6)
Inverter module protection
27
28
P7
Main inverter current protection
29
P8
Auxiliary inverter current protection
30
P9
DC fan protection
31
PL
Main inverter module temp. protection
32
xL0
DC compressor module error
33
xL1
DC bus low pressure protection
34
xL2
DC bus high pressure protection
xL3
Reserve
35
36
xL4
MCE error/synchronization/closed loop
37
xL5
Zero speed protection
38
xL6
Reserve
39
xL7
Phase error protection
Protection should the speed change be greater than 15 Hz before and
40
xL8
after
41
xL9
Protection should the required speed fluctuate by more than 15Hz
RDCI Series – All DC Inverter Outdoor Units
Error or protection type
MALFUNCTION | 5
Note
Only displays on auxiliary unit
Should there be no communication after 20 minutes from
when the unit is first powered up or no communication for
longer than 2 minutes after the 20 minutes initial power up
Once the unit has run for 10 minutes, the unit will allow a
discharge temperature of less than 15 degrees at a pressure
of more than 3.5MPa for 2 minutes. After 2 minutes the
unit will fault and will have to be powered off/ on to reset the
fault.
X represents a system, 1 is
A
system, 2 is B system
X represents a system, 1 is
A
system, 2 is B system
Only displayed on main unit
Only displayed on main unit
Must restart electrical power supply to unit to clear the fault
Must restart electrical power supply to unit to clear the fault
Must restart electrical power supply to unit to clear the fault
Indoor units communication lost for more than 3 munites;
Fault will no clear until the quantity of units are recovered
Air discharging pressure Pc
≤ 0.3MPa
Must restart electrical power supply to unit to clear the fault
Must restart electrical power supply to unit to clear the fault
X represents an auxiliary unit
Should 'P2' fault occur more than 3 times in 60 minutes, the
unit will then display 'H5' fault
X represents a system, 1 is
A
system, 2 is B system
Should 'P6' fault occur more than 3 times in 100 minutes,
the unit will then display 'H6' fault
X represents a system, 1 is
A
system, 2 is B system. Should
'P6' fault occur more than 3 times in 60 minutes, then the
unit will display a 'H4' fault. If 'H4' fault is displayed for more
than 10 minutes, then 'xP6' fault will be displayed
Should 'P9' fault occur more than 3 times in 60 minutes, the
unit will then display 'H9' fault
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
X represents a system, 1 is
A
system, 2 is
6 720 862 438 (2016/04)
B system
B system
B system
B system
B system
B system
B system
B system
B system
B system

Hide quick links:

Advertisement

loading