Emerson Tartarini B/240-FS Series Instruction Manual

Emerson Tartarini B/240-FS Series Instruction Manual

Spring loaded pressure regulators

Advertisement

Instruction Manual
0047EN-B240-IM
September 2010 - Rev. 01
B/240 Series Spring Loaded Pressure regulators
Summary
Introduction ........................................................................
P.E.D. Categories and Fluid Group ...................................
Characteristics ...................................................................
Labelling ............................................................................
Overpressure Protection ....................................................
Transport and Handling .....................................................
Atex Requirements ............................................................
Slam-Shut Controller .........................................................
Dimensions and Weights ...................................................
Operation ...........................................................................
Installation .........................................................................
Startup ...............................................................................
Adjustment .........................................................................
Shutdown ...........................................................................
Periodical Checks ..............................................................
Maintenance ......................................................................
Spare Parts ........................................................................
Troubleshooting .................................................................
Parts List ............................................................................

INTrODuCTION

Scope of manual
This manual provides instructions for installation, startup,
maintenance and spare parts ordering for the B/240 series
spring loaded regulators.
Product Description
The B/240 series regulators are spring loaded single seated,
whit counterbalanced valve disc.
They are usually supplied with safety valve and built in
filter and can be also provided with slam-shut controller for
minimum pressure, maximum pressure or minimum and
maximum downstream pressure.
The regulators of the B/240 series due to their operating
specifications are mainly used in those system where
sudden capacity variations are required, or else, where the
cut-off of the gas distribution is controlled by solenoid valve,
such as for the feeding of burners.
1
2
2
2
3
3
3
3
4
5
6
6
7
7
They can be used with natural gas, and other not aggressive
7
gases.
7
The following versions are available:
8
B/242 • B242-aP: Regulator
8
B/249 • B249-aP: Regulator with slam-shut
9
Versions without relief valve available on request
Tightness cover versions available on request (e.g. B/249-D).
The standard gas pressure devices (regulators and safety
shut-off devices) are those used in the assemblies dealt with
into EN 12186 and EN 12279 and their use has to be under
the provisions into ENs 12186 & 12279.
Fail-to-open stand-alone regulators cannot be used as
a safety accessory according PED 97/23/EC to protect
downstream pressure equipment.
In the pressure regulators (with or without built-in safety
shut-off devices) manufactured by Emerson Process
Management shall be used additionary pressure accessories
(e.g. pilots or filters) manufactured and labeled by Emerson
Process Management.
Emerson Process Management will be not responsible
for any possible inefficiency due to installation of not own
production additionary pressure accessories (e.g. pilots or
filters).
When pressure containing parts of possible built-in safety
shut-off device (SSD) valve and pilot have different
maximum allowable pressures, the SSD is differential
strength type.
Type B/240
Figure 1. Regulator Type B/249

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Tartarini B/240-FS Series

  • Page 1: Table Of Contents

    The B/240 series regulators are spring loaded single seated, Management shall be used additionary pressure accessories whit counterbalanced valve disc. (e.g. pilots or filters) manufactured and labeled by Emerson Process Management. They are usually supplied with safety valve and built in...
  • Page 2: P.e.d. Categories And Fluid Group

    Type B/240 P.E.D. CaTEGOrIES aND FLuID GrOuP Outlet Set Pressure ranges B/242 • B/249: 10 ÷ 75 mbar According to EN 14382, only in integral strength type and Class A configuration (when both over and under pressure B/242-AP • B/249-AP: 50 ÷ 300 mbar protections are set up), the possible built-in safety shut-off Range 300 ÷...
  • Page 3: Overpressure Protection

    Type B/240 OvErPrESSurE PrOTECTION (e.g. : filling/exhausting of fuel gas of internal volume of the isolated part/entire installation with vent lines The recommended maximum allowable pressures are to safe area - 7.5.2 of EN 12186 & 7.4 of EN 12279 ; stamped on the regulator nameplate.
  • Page 4: Dimensions And Weights

    Type B/240 DImENSIONS aND WEIGhTS B/249 • B/249-AP B/242 • B/242-AP ∅ 200 ∅ 125 ∅ 200 FS VERSION FS VERSION Note: The regulator can be installed with vertical or horizontal orientation of the actuator. Figure 4. B/240 Series Dimensions (mm) Weights: B/242 •...
  • Page 5: Operation

    Type B/240 OPEraTION OS/66 Figure 5. B/240 Series Operational Schematic The movements of the diaphragm (D) are transmitted to the valve disc (O) by the stem (S) and the lever (L). The downstream pressure through the pulse pipe (I) exerts a force under diaphragm (D) and this force is counteracted by the adjusting spring (M).
  • Page 6: Installation

    Type B/240 INSTaLLaTION Pressure equipment in subject shall be installed in non-seismic area and hasn’t to • Ensure that the data found on the regulator plate are undergo fire and thunderbolt action. compatible with usage requirements. Clean out all pipelines before installation of •...
  • Page 7: Adjustment

    Type B/240 aDjuSTmENT maINTENaNCE (SEE FIGurE 6) To change the outlet pressure, remove the closing cap (key. 1) and turn the adjusting nut (key. 2) clockwise to increase outlet pressure or counter clockwise to decrease WarNING pressure. Monitor the outlet pressure with a test gauge during the adjustment.
  • Page 8: Spare Parts

    Type B/240 reassembling i. Check diaphragm and if worn or damaged, dismount the diaphragm unit and replace it. Lubricate all seals with “MOLYKOTE 55 M” and be very unscrew register nut (key 4) and then remove spring careful not to damage them when reassembling. (key 6).
  • Page 9: Parts List

    Type B/240 ParTS LIST Description Ring nut Spring Spring holder Spring Relief valve guide Special nut Cover Spring guide plate Diaphragm plate Relief valve stem Diaphragm unit Screw Spring holder O-ring Hub unit Bush Diaphragm PIPE EXTENSION, ONLY FOR OUTLET Body PRESSURES 15 TO 40 mbar Seat...
  • Page 10 Type B/240 SEC. A-A FOR THE VERSIONS WITHOUT RELIEF VALVE MAKE SOLID SPRING KEY 6 11 12 LM/1234 Figure 6. B/240 Series Regulator (continued)
  • Page 11 Type B/240 B/240-FS VERSION B/242 VERSION HIGH PRESSURE VERSION OUTLET PRESSURE UP TO 0.5 bar QL VERSION DETAIL TIGHTNESS COVER VERSION BP DETAIL AP DETAIL LM/1234 Figure 6. B/240 Series Regulator (continued)
  • Page 12 For further information visit: www.emersonprocess.com/regulators The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Tartarini is a mark of O.M.T. Officina Meccanica Tartarini s.r.l., a business of Emerson Process Management.