INSTALLATION & OPERATION MANUAL
O I L C I R C U L AT I N G H E AT I N G S Y S T E M
F O R H A Z A R D O U S L O C AT I O N S
MODEL
OLA

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OLA and is the answer not in the manual?

Questions and answers

Summary of Contents for Hotstart OLA

  • Page 1 216348-000 rev1 INSTALLATION & OPERATION MANUAL O I L C I R C U L AT I N G H E AT I N G S Y S T E M F O R H A Z A R D O U S L O C AT I O N S MODEL...
  • Page 3 IDENTIFYING YOUR SYSTEM IOM216348-000 The HOTSTART heating system is designed to heat fluids for use in marine propulsion, diesel-powered generator sets, locomotives, gas compression or any large-engine applications. The system is pre-wired, pre-plumbed and assembled on steel plate. Each heating system has an identification plate which includes the part number and serial number.
  • Page 4 IMPORTANT SAFETY HOTSTART recommends that a power switch or circuit breaker be located near the heating system INFORMATION for safety and ease of use. • Flameproof joints: Flameproof joints are not intended to be repaired in the field. Do not attempt...
  • Page 5: Table Of Contents

    Control TCR (Temperature Control Relay) | 3.2.3 High-Limit TCR (Temperature Control Relay) | HEATING SYSTEM START-UP | 3.3.1 First Run Procedure | MAINTENANCE AND TROUBLESHOOTING | SYSTEM FAULTS | 4.1.1 Oil Faults | & installation operation manual ola heating system...
  • Page 6: Overview | 1

    (this page intentionally left blank) & installation operation manual ola heating system...
  • Page 7: Overview

    OVERVIEW WARNING System location classification: Before installing the OLA heating system, ensure all system components are suitable for the intended installation location by referring to the location classification labeling attached to the individual system components. HEATING SYSTEM COMPONENTS OOE: Component illustrations are for reference only and are not to scale. See part drawings for dimensions and specifications.
  • Page 8: Operation Overview

    OPERATION OVERVIEW The OLA heating system is intended to maintain optimal oil temperature while the engine or compressor is shut down. The heating system may be activated locally or by optional remote control (see SECOIO 2.5.2). The OLA heating system must be deactivated upon engine start-up.
  • Page 9: Installation

    If the pump is installed above the minimum oil level, a check valve must be installed. Isolation valves: HOTSTART recommends installing full-flow ball valves to isolate the heating system in order to perform service on the system or engine without draining the oil.
  • Page 10: Oil Plumbing Installation

    See Table 1 for HOTSTART OLA oil supply recommendations: 2.1.2 OIL RETURN PUMP HOSE INNER MAX. LINE MAX. ELBOW When installing the OLA oil return line, refer to the INLET DIAMETER LENGTH COUNT following HOTSTART guidelines: 1/2 inch 1 inch 20 feet •...
  • Page 11: Oil Plumbing Illustration (Engine)

    OIL SUPPLY SECOIO 2.1.1 OIL RETURN SECOIO 2.1.2 ISOLATION VALVE COMPONENT DESCRIPTION USER SUPPLIED CHECK VALVE USER SUPPLIED FULL FLOW ISOLATION VALVE OIL PUMP OIL HEATING ELEMENT USER SUPPLIED FULL FLOW ISOLATION VALVE & installation operation manual ola heating system...
  • Page 12: Oil Plumbing Installation | 4 4

    OIL SUPPLY SECOIO 2.1.1 ISOLATION VALVE COMPONENT DESCRIPTION USER SUPPLIED CHECK VALVE USER SUPPLIED FULL FLOW ISOLATION VALVE OIL PUMP OIL HEATING ELEMENT USER SUPPLIED FULL FLOW ISOLATION VALVE OPTIONAL USER SUPPLIED PRV & installation operation manual ola heating system...
  • Page 13: Mounting

    Unless mounted properly, the heating system will be unstable. 2.4.1 TANK AND PUMP Figure 4. OLA underside, showing 1.25 ″ NPT main power entrance (A) and 0.5 ″ NPT customer interface wiring entrance (B). 2.5.1 MAIN POWER SUPPLY Connect the specified power from the customer- supplied circuit breaker to the terminal blocks located in the main control box.
  • Page 14: Customer Interface Connections

    Main power terminal block Remote On/Off Figure 5. Main power supply and customer interface connections 24 V DC shutdown as shown in the OLA control box. Reference electrical schematic Main power ground drawing for proper wiring locations; the following illustrations are terminal block Fault signal typical customer interface locations.
  • Page 15: Motor Rotation Check

    OOICE! Do not run PUMP INLET PUMP OUTLET the motor/pump assembly dry for more than five Figure 6. Typical OLA pump assembly. Note that the pressure relief seconds at a time. valve cap must always point toward the inlet side of pump. &...
  • Page 16: System Components

    11 12 13 14 A2- 13 14 A2- Figure 7. OLA motor protection switch (left), showing stop/off (A) and reset/on (B) buttons. To reset the MPS, the heating system must MPS1 be switched off and either the reset button or the MPS reset/on button must be pressed.
  • Page 17: First Run Procedure

    HEATING SYSTEM START-UP the desired temperature setting for engine oil. HOTSTART recommends a control temperature on TCR1 of 104 °F (40 °C). The high-limit temperature WARNING setting on TCR2 should be set at 194 °F (90 °C). Hazardous voltage: Before wiring, servicing or cleaning See SECOIO 3.2.2 and SECOIO...
  • Page 18: Plumbing Connections

    4.2.4 MAGNETIC CONTACTORS Magnetic contactors are used as voltage switching controls for motors and heating elements in HOTSTART heating systems. The contactors use 120 volt or 240 volt coils. To test for failure, check for continuity across the coil connections; an open or direct-short reading indicates a failed contactor coil.
  • Page 19: Temperature Control Relay

    TCR1 TCR2 shock. Figure 8. Control (TCR1) and high-limit (TCR2) TCR showing If the OLA heating system does not maintain the desired 11 12 11 12 terminals T1, T2 and T3. preset control temperature or signals a high-limit 13 14 A2-...
  • Page 20: Recommended Maintenance

    If your pump motor has provisions for relubrication, refer to the pump motor manufacturer’s relubrication recommendations. Refer to the pump motor nameplate for lubrication type. & installation operation manual ola heating system...
  • Page 21: Troubleshooting

    Control TCR set point too low Adjust set point for control TCR. See SECOIO 3.2.2. Check TCR and RTD. See SECOIO 4.2.9 RTD failure Check TCR and RTD. See SECOIO 4.2.9. RTD cable failure & installation operation manual ola heating system...