3.2 - Duct connection

30RQSY units can be installed inside a building and
connected to a air distribution duct network:
-
Air heat exchanger side, at the fresh air suction side for
30RQSY 039 to 078 units
-
Fan discharge side at the evacuation side of the treated
air by the unit heat exchanger (30RQSY 039 to 160).
For the precise dimensions of this connection interface please
refer to the dimensional drawings for the units.
3.2.1 - Standard unit suction connection
30RQSY 039 to 078 units are supplied with a sleeve that
allows connection of an air heat exchanger suction duct.
Provide a removable window on the suction duct to allow
the maintenance of the sensor (see figure above).
For units 30RQSY 050 to 078 the air heat exchanger is on
two unit sides. It is therefore necessary to install two
additional brackets to allow connection of the heat exchanger
suction duct.
These parts are inside the machine and fixed to the riser (as
shown on the diagram below) with plastic collars.
10
Location of the air
temperature sensor
Specific connection precautions for sizes 30RQSY 050 to 078
Air inlet
Air inlet
minimum
All dimensions are in mm.
3.2.2 - Fan discharge connection
A square flange is supplied mounted on the unit. An available
standard round flange can easily be installed at the fan
discharge, if the installer prefers the use of a round connection
duct.
The unit is supplied with a grille on the discharge side. This
grille has to be removed before connection to the duct system.
It is advisable to make the connection to the duct system
with a flexible sleeve. If this recommendation is not observed,
a lot of vibration and noise may be transmitted to the building
structure.