Motor Starter Protector + 3Rw30 Soft Starter - Siemens SIRIUS Configuration Manual

Load feeders
Hide thumbs Also See for SIRIUS:
Table of Contents

Advertisement

3.9

Motor starter protector + 3RW30 soft starter

CLASS 10, type of coordination 1,
Standard three-phase motor
4-pole at
400 V AC
1)
Standard
Motor current
output
I
P
kW
A
Short-circuit breaking capacity I
1,5
3,6
Short-circuit breaking capacity I
1,5
3,6
3
6,5
4
8,5
5,5
11,5
7,5
15,5
Short-circuit breaking capacity I
11
22
15
29
18,5
35
3)
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible. 3RA2921-1BA00 link
module can only be used with screw terminals.
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
1)
of the protected motor.
Rated currents taken into account at 40 °C ambient temperature. Rated control supply voltage 230 V AC, 50 Hz. Other
2)
control voltages are also possible.
Discrete mounting only, without a link module.
3)
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
Setting range
Motor starter
Overload release
protector
Motor starter
Motor protection
protector
A
Order No.
= 50 kA
q
2,8 ... 4,0
3RV2011-1EA10
= 5 kA
q
3,5 ... 5,0
3RV2011-1FA10
5,5 ... 8,0
3RV2011-1HA10
7,0 ... 10,0
3RV2011-1JA10
9,0 ... 12,5
3RV2011-1KA10
14 ... 20
3RV2021-4BA10
= 55 kA
q
20 ... 25
3RV2021-4DA10
27 ... 32
3RV2021-4EA10
34 ... 40
3RV2021-4FA10
Selection tables 400 V AC
3.9 Motor starter protector + 3RW30 soft starter
Soft starter
2)
Order No.
3RW3003-1CB54
3RW3013-1BB14
3RW3014-1BB14
3RW3016-1BB14
3RW3017-1BB14
3RW3018-1BB14
3RW3026-1BB14
3RW3027-1BB14
3RW3028-1BB14
Size
MSP / 3RW30
S00/- (22.5 mm)
S00/S00
S00/S00
S00/S00
S00/S00
S0/S00
S0/S0
S0/S0
S0/S0
47