16. Dip Switch Setting

BM1 introduction

BM1_1
Control type selection
BM1_2
BM1_3
Outdoor unit Model selection
BM1_4
BM1_5
BM1_6
Power selection
BM1_7
Reserved
BM1_8
IO board selection

BM2 introduction

BM2_1
Heat exchange unit type
BM2_2
Control mode selection
BM2_3
HU electrical heating control mode
Water flow switch fault shielding
BM2_4
selection
BM2_5
PC and MODBUS selection
BM2_6
Running mode selection
BM2_7
BM2_8
Hot water mode selection

bridge instruction

CJ1:
Short it before power ON-- PCB check its function (used for factory production. Short it after power ON-- time short
function, 60 seconds become to 1 second. CJ2: Reserved
OFF Wired controller control (default)
ON IO board control
[2]
[3]
[4]
[5]
Outdoor unit Model selection
OFF OFF ON
OFF AU082FYCRA(HW)
OFF ON
OFF OFF AU112FYCRA(HW)
OFF ON
OFF ON AU162FYCRA(HW)
OFF Single phase (default)
ON Three phases
OFF Reserved (default)
ON Reserved
OFF No IO board (default)
ON
Connect with IO board
OFF
Air condition heat exchange unit(default)
ON
Hot water heat exchange unit
OFF
Networking (default)
ON
2-way valve linkage
OFF
HU electrical heating auto control (default)
ON
HU electrical heating force close
OFF
Normal detection (default)
Shield for a short time, then resume normal
ON
detection
OFF
PC monitor (default)
ON
MODBUS
[6]
[7] Running mode selection
OFF
OFF Normal mode (default)
OFF
ON Powerful mode
ON
OFF Silent mode
OFF
No hot water (default)
ON
Hot water mode
56