Ten input monitor module

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SK-Mon-10 Ten Input Monitor Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum IDC
Wiring Resistance:
Maximum IDC Voltage:
Maximum IDC Current:
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Mon-10 Ten Input Monitor Module is intended for use in an intelligent
alarm system. Each monitor module is intended to interface between a control
panel and normally open contact devices, such as pull stations. A common
SLC input is used for all modules, and the initiating device loops share a
common supervisory supply and ground. Otherwise, each monitor operates
independently from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first mod-
ule from 01 to 150 (01 to 90 on panels that support up to 99 addresses).
The remaining modules are automatically assigned to the next nine higher
addresses. Provisions are included for disabling a maximum of two unused
modules to release the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the LEDs to blink,
latch on, or latch off.
ShIPPED ON BOARD:
(1) Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
INCLUDED:
(6) 1 x 4 Terminal Blocks
(2) 1
1
(4) Machine Screws
(3) Shunts
(2) Nuts
SK-460-009
15-32 VDC
3.5 mA
55 mA (assumes all ten LEDs solid on)
32°F to 120°F (0°C to 49°C)
10 to 93% Non-condensing
6.8˝ H x 5.8˝ W x 1.25˝ D
IDP-ACB Cabinet and Chassis
12-18 AWG
1500 Ohms
10.2 VDC
240 µA (each circuit)
/
˝ (32mm) Stand offs
4
(10) 47k Ohm
End of Line Resistors
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel.
COMPONENTS
The following is a description of the SK-Mon-10 mounting framework:
One or two SK-Mon-10 modules can be installed in an IDP-ACB cabi-
net.
The IDP-ACB cabinet has a built-in chassis that will accommodate one or two
SK-Mon-10 modules.
FIGURE 1: IDP-ACB CABINET
The front SK-Mon-10 module positions of each chassis are offset below the
rear SK-Mon-10 module positions so that all of the status indicators are visible.
For cabinet dimensions refer to the IDP-ACB instruction manual.
C0202-00
1
7550 Meridian Circle, Maple Grove, MN 55369-4927
763.493.6455, 800.328.0103; Fax: 763.493.6475
http://www.silentknight.com
C0234-05
I56-3443-000

Advertisement

loading

Summary of Contents for Honeywell SK-Mon-10

  • Page 1 The IDP-ACB cabinet has a built-in chassis that will accommodate one or two SK-Mon-10 modules. GENERAL DESCRIPTION The SK-Mon-10 Ten Input Monitor Module is intended for use in an intelligent FIGURE 1: IDP-ACB CABINET alarm system. Each monitor module is intended to interface between a control panel and normally open contact devices, such as pull stations.
  • Page 2 The module is shipped in Class B position, remove shunt for Class A. When operating in Class A, alternate modules are paired together (+0/+1, Step 1: Insert the bottom of the SK-Mon-10 module down into a rear slot on +2/+3, +4/+5, +6/+7, +8/+9), resulting in a total of five modules. For the chassis.
  • Page 3 FIGURE 5: TYPICAL INITIATING DEvICE CIRCUIT CONFIGURATION – CLASS B, STYLE B. BASE ADDRESS CONNECT MODULES TO 6 7 8 9 6 7 8 9 LISTED COMPATIBLE SILENT KNIGHT CONTROL PANELS ONLY RESISTOR ELR-47K CLASS B IDC (TYPICAL) A/B SLCT COM LOSS DISABLE 1 DISABLE 2...