Page 1
Instruction Booklet IB48083 Effective August 2014 Vacuum interrupter replacement SLN018, SL12, SL15, and SJ contactors Bottle Stud Bottle Nuts Line Terminal Pivot Plate Contact Spring Crossbar Kickout Springs Kickout Spring Lever Shunt VI Bottle Kickout Spring Lever Adjustment Screw VI Brace...
Page 2
Instruction Booklet IB48083 Vacuum interrupter replacement SLN018, SL12, SL15, and SJ contactors Effective August 2014 4. Remove control transformer primary fuses 14. Install contact springs and cups onto the top stems, with cup on (Classic Ampgard only). top, flange down. See Figure 4.
Page 3
Instruction Booklet IB48083 Vacuum interrupter replacement SLN018, SL12, SL15, and SJ contactors Effective August 2014 22. Turn the center pole bottle nuts clockwise until they are 0.120 ± 0.005 inches from the pivot plate. This is the overtravel gap. See Figure 5. Lock the bottle nuts with a screwdriver...