Vacuum interrupter replacement contactors

Advertisement

Instruction Booklet IB48083
Vacuum interrupter replacement
SLN018, SL12, SL15, and SJ contactors
Kickout Spring Lever
Kickout Spring Lever
Adjustment Screw
Figure 1. Open Contactor
 DANGER—HAZARDOUS VOLTAGE
READ AND UNDERSTAND THESE INSTRUCTIONS
BEFORE ATTEMPTING REPLACEMENT OF VACUUM
INTERRUPTERS. THIS EQUIPMENT SHALL BE
INSTALLED AND SERVICED ONLY BY QUALIFIED
ELECTRICAL PERSONNEL. A QUALIFIED PERSON IS ONE
WHO IS FAMILIAR WITH THE CONSTRUCTION AND
OPERATION OF THIS EQUIPMENT AND WHO IS AWARE
OF THE HAZARDS INVOLVED.
Effective August 2014
Bottle Stud
Pivot Plate
Crossbar
Kickout Springs
Operating Coil
Control Board
Bottle Nuts
Magnet
Armature
Vacuum interrupter
subassembly replacement
If it becomes necessary to replace vacuum
interrupters, proceed as follows:
1. De-energize the contactor. Remove to a
workbench.
2. Remove the top barrier assembly
(four hex-head bolts, Classic AmpgardT only).
3. Unbolt the shunts on the line side of the
bottles. See Figure 2.
Figure 2.
Line Terminal
Contact Spring
Shunt
VI Bottle
VI Brace
Load Terminal
Bottle Bolt

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SLN018 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eaton SLN018

  • Page 1 Instruction Booklet IB48083 Effective August 2014 Vacuum interrupter replacement SLN018, SL12, SL15, and SJ contactors Bottle Stud Bottle Nuts Line Terminal Pivot Plate Contact Spring Crossbar Kickout Springs Kickout Spring Lever Shunt VI Bottle Kickout Spring Lever Adjustment Screw VI Brace...
  • Page 2 Instruction Booklet IB48083 Vacuum interrupter replacement SLN018, SL12, SL15, and SJ contactors Effective August 2014 4. Remove control transformer primary fuses 14. Install contact springs and cups onto the top stems, with cup on (Classic Ampgard only). top, flange down. See Figure 4.
  • Page 3 Instruction Booklet IB48083 Vacuum interrupter replacement SLN018, SL12, SL15, and SJ contactors Effective August 2014 22. Turn the center pole bottle nuts clockwise until they are 0.120 ± 0.005 inches from the pivot plate. This is the overtravel gap. See Figure 5. Lock the bottle nuts with a screwdriver...
  • Page 4 Instruction Booklet IB48083 Vacuum interrupter replacement SLN018, SL12, SL15, and SJ contactors Effective August 2014 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com © 2014 Eaton All Rights Reserved Eaton is a registered trademark. Printed in USA All other trademarks are property Publication No.

This manual is also suitable for:

Sl12Sl15Sj

Table of Contents