Carrier 38AUM Series Installation, Operation & Maintenance Manual page 6

Air cooled condensing units–50hz
Table of Contents

Advertisement

BASE UNIT DIMENSIONS – 38AUM Series Size D16
Height
Unit
Unit
38AUM
Weight (kg)
D16
332.0
NOTES:
1. Minimum clearance (Local codes or jurisdiction may prevail):
A. Bottom to combustibles surfaces: 0 Inches
B. Outdoor coil, for proper airflow: 36 inches one side, 12 inches the other. The side getting the greater clearance is optional.
C. Overhead: 60 inches, to assure proper outdoor fan operation.
D. Between units: control box side: 42 inches per NEC.
E. Between unit and ungrounded surfaces: Control box side, 36 inches per NEC.
F. Between unit and block or concrete walls and other grounded surfaces: Control box side 42 inches per NEC.
2. With exception of the clearance for the outdoor coil as stated in note 1B, are movable fence or barricade requires no clearance.
3. Units may be installed on combustible floor made from wood or Class A, B or C roof covering material.
TOP VIEW
FRONT
Center of Gravity
(mm)
(mm)
H
X
Y
Z
1339
965.2
482.6
431.8
LEFT SIDE VIEW
- Center Of Gravity
- Direction of Air Flow
Service Valve
Connections
Suction
Liquid
1-3/8
1/2
Page 6