Download Print this page

System Sensor SpectrAlert Advance Series Installation And Maintenance Instructions page 2

Selectable output strobes, horns, and horn/strobes

Advertisement

Figure 1. Wiring 2-Wire produCTS:
INPUT
FROM
FACP
OR
PRIOR
DEVICE
+
Figure 2. Wiring 4-Wire produCTS:
INPUT
FROM
FACP OR
PRIOR
STROBE
+
+
INPUT FROM
FACP OR PRIOR HORN
Figure 3. SHorTing Spring:
NOTE: A shorting spring is provided between terminals 2 and 3 of the mount-
ing plate to enable wiring checks after the system has been wired, but prior
to installation of the final product. This spring will automatically disengage
when the product is installed, to enable supervision of the final system.
CandeLa SeLeCTion
Adjust the slide switch on the rear of the product to position the desired can-
dela setting in the small window on the front of the unit. All products meet
the light output profiles specified in the appropriate UL Standards. For K series
products used outdoors at low temperatures, listed candela ratings must be re-
duced in accordance with Table 2. Use Table 1 to determine the current draw
for each candela setting. WIRING DIAGRAMS
NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work
on either 12V or 24V power supplies. The products are not listed for 12V op-
erating voltages when set to any other candela settings. For 4-Wire products,
total current draw may be determined by adding current draw for the specific
candela selection in Table 1 with the current draw for the specific horn selec-
tion in Table 3.
D690-03-00
TabLe 1. STrobe CurrenT draW (
OUTPUT
TO
NEXT
DEVICE
OR EOL
+
A0367-01
OUTPUT
TabLe 2. CandeLa deraTing:
TO NEXT
STROBE
OR EOL
+
+
OUTPUT TO NEXT
HORN OR EOL
A0366-00
Horn SeLeCTion
Turn the rotary switch on the back of the product to the desired setting. For
horn and 4-wire horn/strobe products, the current draw for each setting is
listed in Table 3. For 2-wire horn/strobe products (P2 series), current draws
are listed in Tables 4 and 5. The sound output measurement for each horn
setting is shown in Table 6.
TabLe 3. Horn CurrenT draW (
SHORTING SPRING
A0368-00
NOTE: In positions 7, 8, and 9, temporal coding must be provided by the NAC.
If the NAC voltage is held constant, the horn output will remain constantly on.
Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.
2
Candela
Standard Candela Range
High Candela Range
Listed Candela
15
15/75
30
75
95
110
115
135
150
177
185
Pos Sound Pattern dA Out
1
Temporal
High
2
Temporal
Medium
3
Temporal
Low
4
Non-temporal High
5
Non-temporal Medium
6
Non-temporal Low
7
Coded
High
8
Coded
Medium
9
Coded
Low
ma
) For S, SC, p4 & pC4 SerieS:
8–17.5 Volts
16–33 Volts
DC
FWR
DC
15
123
128
66
15/75
142
148
77
30
NA
NA
94
75
NA
NA
158
95
NA
NA
181
110
NA
NA
202
115
NA
NA
210
135
NA
NA
228
150
NA
NA
246
177
NA
NA
281
185
NA
NA
286
Candela rating at –40°F
(K Series Outdoor Applications Only)
Do not use below 32°F
44
70
110
115
135
150
177
185
) For H, p4 & pC4 SerieS:
ma
8–17.5 Volts
16–33 Volts
DC
FWR
DC
57
55
69
44
49
58
38
44
44
57
56
69
42
50
60
41
44
50
57
55
69
44
51
56
40
46
52
I56-2769-015R
FWR
71
81
96
153
176
195
205
207
220
251
258
FWR
75
69
48
75
69
50
75
69
50

Advertisement

loading

This manual is also suitable for:

Spectralert advance p2rSpectralert advance p2rhSpectralert advance p2rkSpectralert advance p2rhkSpectralert advance p2wSpectralert advance p2wk ... Show all