Download Print this page
System Sensor SpectrAlert S1224MCK Installation And Maintenance Instructions
System Sensor SpectrAlert S1224MCK Installation And Maintenance Instructions

System Sensor SpectrAlert S1224MCK Installation And Maintenance Instructions

Selectable output outdoor strobes, horn and horn/strobes

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SpectrAlert Selectable Output
Outdoor Strobes, Horn and Horn/Strobes
For use with the following models:
Strobe - 12/24 volt:
S1224MCK
Combo - 12/24 volt:
P1224MCK
Horn - 12/24 volt:
H12/24K
"K" model series are outdoor rated when installed with System Sensor WBB.
The Products to which this manual applies may be covered by one or more of the following U.S. Patent numbers:
5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,133,843; 6,522,261; 6,661,337; 6,793,375; 6,822,400; 5,931,569; 6,833,783; 6,838,997;
Specifications
Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified)
Electrical
Horns, Strobes, and
Horn/Strobes Voltages:
Operational Voltage Ranges:
Synchronous Applications
with MDL Module:
NOTE: Horn units will operate on walk tests with on-time durations of .25 sec. or greater.
Flash Rate:
K Series Operating Temperature:
Selectable Light Outputs:
12/24 Volt Applications:
24 Volt Application:
Sound Output:
Listings:
Note for Strobes: Do not exceed; 1) 8-17.5 or 16-33 voltage range limit; 2) maximum number of 70 strobe lights when connecting the MDL Sync module
with a maximum line impedance of 4 ohms per loop and; 3) maximum line impedance as required by the fire alarm control manufacturer.
The models S1224MCK and P1224MCK incorporate a patented voltage booster design that has a more consistent flash bulb voltage over the range of candela
selections. The benefit to the customer is a high quality strobe device.
General Description
The SpectrAlert series notification appliances are designed to
meet the requirements of most agencies governing these devices,
including: NFPA, ADA, The National Fire Alarm Code, UL, and
ULC. Also, check with your local Authority Having Jurisdiction
for other codes or standards that may apply.
The SpectrAlert series can be installed in systems using 12- or 24-
volt panels having DC or full-wave rectified (FWR) power supplies.
The series can also be installed in systems requiring synchroniza-
tion (module MDL or compatible equivalent required) or systems
that do not require synchronization (no module required).
NOTICE: This manual shall be left with the owner/user of this equipment.
Fire Alarm System Considerations
Temporal and Non-Temporal Coded Signals:
The American National Standards Institute and the National Fire
Alarm Code require that all horns used for building evacuation in-
stalled after July 1, 1996, must produce Temporal Coded Signals.
Signals other than those used for evacuation purposes do not have
to produce the Temporal Coded Signal. Temporal coding is accom-
plished by interrupting a steady sound in the following manner:
D900-37-00
Regulated 12 DC/FWR and Regulated 24 DC/FWR
12V=8-17.5 Volts; 24V=16-33 Volts
12V=9-17.5 Volts; 24V=17-33 Volts
1 flash per second
S trobe, horn and horn/strobe models are indoor and outdoor listed, having a temperature
range of –40° F to 150.8° F (–40° C to 66° C)
A ll models are indoor/outdoor listed, strobes per UL 1971 and UL 1638, horns per UL 464.
All candelas are selectable via a manual slide switch.
15 or 15/75 candela
30, 75, 110 candela
1 5/75 is listed at 15 candela per UL 1971 but will provide 75 candela on axis (straight ahead).
15, 30, 75, or 110 are rated for that candela.
S ound output levels are established at Underwriters Laboratories in their reverberant room.
Always use the sound output specified as UL Reverberant Room when comparing products.
UL S3593/S5512 (Strobe); UL S4011 (Combo); UL 1638 and UL 1971 (Strobe); UL50 (Horn)
Power Supply Considerations
Panels typically supply DC filtered voltage or FWR (full-wave
rectified) voltage. The system design engineer must calculate the
number of units used in a zone based on the type of panel supply.
Be certain the sum of all the device currents do not exceed the
current capability of the panel. Calculations are based on using
the device current found in the subsequent charts and must be
the current specified for the type of panel power supply used.
Wire Sizes
The designer must be sure that the last device on the circuit has
sufficient voltage to operate the device within its rated voltage.
When calculating the voltage available to the last device, it is nec-
essary to consider the voltage drop due to the resistance of the
wire. The thicker the wire, the less the voltage drop. Generally, for
purposes of determining the wire size necessary for the system, it
is best to consider all of the devices as "lumped" on the end of the
supply circuit (simulates "worst case").
1
firealarmresources.com
3825 Ohio Avenue, St. Charles, Illinois 60174
1
1
1
1
/
Sec.
/
Sec.
/
Sec.
/
Sec.
2
2
2
2
On
Off
On
Off
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
1
1
/
Sec.
1
/
Sec.
Repeats
2
2
On
Off
I56-2257-005R

Advertisement

loading

Summary of Contents for System Sensor SpectrAlert S1224MCK

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS SpectrAlert Selectable Output Outdoor Strobes, Horn and Horn/Strobes 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 For use with the following models: www.systemsensor.com Strobe - 12/24 volt: S1224MCK Combo - 12/24 volt: P1224MCK Horn - 12/24 volt: H12/24K “K” model series are outdoor rated when installed with System Sensor WBB. The Products to which this manual applies may be covered by one or more of the following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,133,843; 6,522,261; 6,661,337; 6,793,375; 6,822,400; 5,931,569; 6,833,783; 6,838,997; Specifications Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified) Electrical Horns, Strobes, and...
  • Page 2 Figure 1C: Horn Current Draw Measurements (RMS): Typical wire size resistance: 18 AWG solid: Approximately 8 ohms/1,000 ft. 16 AWG solid: Approximately 5 ohms/1,000 ft. Selectable Horn Tones 14 AWG solid: Approximately 3 ohms/1,000 ft. Temporal Electromechanical 12 AWG solid: Approximately 2 ohms/1,000 ft. Volume 3000 Hz Interrupted Example: Assume you have 10 devices on a zone and each re- High Electromechanical quires 50 mA average and 2000 Ft. of 14 AWG wiring (total Volume 3000 Hz Interrupted length=outgoing +return). The voltage at the end of the loop is...
  • Page 3 Candela Selections: System Operation – Non-Synchronized Devices: Figure 2: For strobe candela selection, adjust slide Figure 4a. Any combination of models powered by a switch located on the rear of the product while watch- 2-wire circuit: ing the viewing window on the side of the reflector. HORN HORN/STROBE STROBE ONLY...
  • Page 4 Figure 8: Removal of horns and strobes from Typical outdoor mounting with universal plate: mounting plates: To remove units from mounting plates, insert Quick Click Re- moval Tool as shown to unlock snap. While pushing in Removal Tool to release the snap, pull back on the horn/strobe. Hinge the horn/strobe module, disengage the Locking Rib, and lift the horn/ strobe away from the mounting plate. PLASTIC SNAP LEVER INSERT REMOVAL TOOL A0120-00 1. Mount WBB in desired location. 2. For SpectrAlert models, mount plate to back box using 4 #8- A0115-00 TAB SLOT 32...

This manual is also suitable for:

Spectralert p1224mckSpectralert h12kSpectralert h24k