AUDAX TOP ErP
2

AUDAX TOP 6 - 8 - 12 ErP FEATURES (MONO-PHASE)

6 kW, 8 kW and 12 kW mono-phase inverter air/water heat
pumps for winter and summer air conditioning. The galvanised
steel structure makes the machines particularly suitable for
outdoor installation.
Main components:
• Control Panel - standard supply - which enables you to pro-
gram the machine and also functions as a room temperature/
humidity sensor. It also displays the error codes in the event
of malfunctions;
• R410A refrigerant gas (pre-loaded in the machine);
• Twin Rotary compressor with hybrid inverter activation in
direct current with PAM (Pulse Amplitude Modulation) and
PWM (Pulse Width Modulation) logic to offer improved
reliability, low energy consumption and vibration-free opera-
tion in all operating conditions and acoustic insulation with
sound-absorbing materials.
• cooling circuit including a compressor and air/gas refrigerant
finned coil, two-way electronic throttle valve, refrigerant gas/
water insulated stainless steel plate heat exchanger, 4-way
reversing valve (reversible heat pump cycle or cooling cycle
operation);
• variable speed fan with a 3-blade impeller characterised by an
innovative profile designed to guarantee better distribution of
air and contained sound levels (AUDAX TOP 6 - 8 ErP);
• double variable speed fan with a 3-blade impeller characterised
by an innovative profile designed to guarantee better distribu-
tion of air and contained sound levels (AUDAX TOP 12 ErP);
• system low energy consumption pump and flow switch to
ensure there is sufficient water circulation to guarantee correct
operation of the hydronic and cooling circuits;
• 2 litre internal expansion vessel (AUDAX TOP 6 - 8 ErP);
• 3 litre internal expansion vessel (AUDAX TOP 12 ErP);
• 3 bar system safety valve;
• included and standard supply are the water Y filter 1", vibra-
tion-dampening devices, condensate drain fittings and cable
clamp to pass electric cables;
• flow and return 1" M hydraulic connections situated at the
rear;
• electronic management system equipped with various sensors
situated in key positions of the cooling circuit to electronically
detect the system's operating status. The system's flow water
temperature is detected by means of a probe;
• option to pilot a 3-way diverter valve directly from AUDAX
TOP ErP for D.H.W. production heating and an external
booster pump on the system;
• maximum system water flow temperature up to 60 °C;
• operation up to outdoor air temperature of -20°C in winter
and +46°C in summer;
• protection against freezing up to -10°C as a result of periodic
activation of the pump and AUDAX TOP ErP cooling circuit
(with power supply voltage);
• IPX4 electrical insulation rating.
System solutions:
• Standalone system with AUDAX TOP ErP and integrative
resistance;
• can be coupled to a separate storage tank for DHW;
• can be coupled to a boiler via the System manager;
• can be coupled to a boiler and the solar heating system via the
System manager.
• can be installed as a set configuration with the System manager.
Is available in the model:
• AUDAX TOP 6 ErP
code 3.025557
• AUDAX TOP 8 ErP
code 3.025558
• AUDAX TOP 12 ErP
code 3.025560
EC Declaration Of Conformity.
5