Routine Maintenance; Periodical Maintenance; Service Operations To Be Carried Out By Qualified Technicians Or By The Manufacturer; Troubleshooting - Zanotti GS Series Use And Maintenance Instructions

Touch control
Hide thumbs Also See for GS Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 17
12

Routine maintenance

Good operation of the unit requires the condenser to be cleaned periodically (frequency of cleaning depends
on the environment where the unit is installed).
Turn off the unit and clean it by blowing air from the inside outwards. Should no air jet be available, use a long-
haired brush and work on the outside of the condenser.
In case of water-cooled condensers have the unit cleaned by a plumber with special descaling agents.
W AR NI NG
Use safety gloves to protect your hands from possible cuts.
W AR NI NG
Disconnect the unit before w orking on it.
12.1

Periodical maintenance

Periodically check wear condition of electrical contacts and remote switches; if necessary replace them.

12.2 Service operations to be carried out by qualified technicians or by the manufacturer

Following operations shall be carried out by qualified technicians or by the manufacturer exclusively. Under
no circumstances the user is allowed to:
replace electrical components
work on the electric equipment
repair mechanical parts
work on the refrigerating system
work on the control panel, ON/OFF and emergency switches
work on protection and safety devices.

12.3 Troubleshooting

During operation following troubles may occur:
1. Compressor stops. The unit is equipped with an overtemperature device which stops the
compressor every time the max. allowable temperature of motor windings is exceeded.
Possible causes are:
2. Ice forms on the evaporator preventing air from flowing regularly.
ATTEN TI ON
Do not use either hot w ater or any pointed, cutting, m etal objects to remove ice blocks.
3. Display does not light up. Check:
4. Unit does not start operating when pressing ON/OFF key (the display is turned on): check
28
- insufficient ventilation of the room where the unit is installed;
- anomaly in mains voltage;
- faulty operation of condenser fan.
Device reset is automatic.
Possible causes are:
- the door is opened too frequently;
- faulty operation of evaporator fan;
- faulty solenoid valve (in models with hot gas defrost);
- faulty defrost heater (in models with electric defrost);
- faulty defrost process. In this case some measures can be taken:
increase defrost termination temperature by some degrees, increase number of
defrosts.
- if there is power to the unit;
- if mains cable is connected properly;
- fuses inside the electric panel
microdoor connection keeping in mind that the switch contact must be closed when
the door is closed.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gs 1Gs 3Gs 2

Table of Contents