Common Motor Terminal Cubicle - ABB ACS800 Hardware Manual

1.5 to 2000 kw inverter modules
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

62

Common motor terminal cubicle

Instead of direct cabling from each inverter module to the motor, it is also possible to
build a common motor terminal cubicle.
WARNING! If a common motor terminal cubicle is constructed, the inverter modules
must be equipped with the +E205 option (internal du/dt filters).
Note that the distance from both modules to the common output should be of roughly
equal length.
Inverter unit cubicle
PE
U2
V2
W2
Common motor terminal
cubicle
M
U1
V1
3~
W1
PE