GE EntelliGuard G Application Manual page 71

Hide thumbs Also See for EntelliGuard G:
Table of Contents

Advertisement

DET-653C
24-May-12
Digit 13 – Bell Alarm/Trip Annunciation
Bell Alarm and Trip Annunciation
Bell Alarm Contact (1NO/1NC) with Lockout (BACL)
Mechanical Operations Counter (MOC)
Bell Alarm Contact (1NO/1NC) with Lockout and MOC
RTC Power Rated Contacts on SD*
RTC Signal Rated (Hi-Fi) Contacts on SD*
RTC Signal Rated (Hi-Fi) Contacts through Trip Unit**
BACL and RTC Power Rated Contacts on SD*
BACL and RTC Signal Rated (Hi-Fi) Contacts on SD*
BACL and RTC Signal Rated (Hi-Fi) through Trip Unit**
BACL, MOC and RTC Power Rated on SD*
BACL, MOC and RTC Signal Rated on SD*
BACL, MOC and RTC Signal Rated (Hi-Fi) through Trip
Unit**
MOC and RTC Power Rated on SD*
MOC and RTC Signal Rated on SD*
MOC and RTC Signal Rated (Hi-Fi) through Trip Unit**
Blank/none
BACL = Bell Alarm Contact with Lockout
RTC = Ready To Close Contacts
**In order to output the RTC contact output via Trip Unit (options 3, F, J,
M) a communications package must be selected in Advanced Features
(Code 19/Step 16); this requires Secondary Disconnect Block B.
**If a UL or ANSI Switch is selected, the (Hi-Fi Through Trip Unit) is not
valid (Options 3, F, J, M).
**RTC Through the Trip Unit is not a valid option for Switches. Bell Alarm
Contact with Lockout comes with the Trip Unit set to Manual LO
Enabled.
• The term "Hi-Fi" refers to gold-plated contacts use for signal level
outputs (10mA minimum - 100mA maximum, 5-30Vdc, 125vac).
• Option "B", "I", "2", "3", "K", "L", "M", and "X" are the only valid options
when a Switch is selected in Digit 2.
Digit 14 – Key Interlock
Key Interlock (Breaker Mounted)
Castell Key Interlock
Kirk Key Interlock
Ronis Key Interlock
Pushbutton Padlock Device
Castell Key Interlock and Push Button Padlock
Device
Kirk Key Interlock and Push Button Padlock Device
Ronis Key Interlock and Push Button Padlock Device
Blank/none
• This option provides factory installed interlocking devices for
installation between separate circuit breakers (baseplates and
mechanism). This safeguard ensures that a circuit breaker cannot be
closed unless the dedicated key has been inserted and secured
within the lock.
• If selecting a Draw Out Breaker (Digit 6), consider putting the Key
Interlock on the Cassette versus the breaker. This enables the ability
to swap breakers without having to change the key interlocks.
• Locks and Keys are NOT Supplied by GE.
©2012 General Electric All Rights Reserved
Code
A
B
C
1
2
3
D
E
F
G
H
J
K
L
M
X
Hi-Fi = High Fidelity
SD = Secondary Disconnect
Code
C
K
R
L
1
2
3
X
EntelliGuard
Digit 15 – Mechanical Interlocks
Mechanical Interlocks
Blank/None DEFAULT
Mechanical Interlock - Type A
Mechanical Interlock - Type B
Mechanical Interlock - Type C
Mechanical Interlock - Type D
Some installations use multiple power sources that are required to supply
energy simultaneously, alternately, or, in a specified sequence.
EntelliGuard G Circuit Breakers can be used to interconnect these sources
and be electrically and mechanically interlocked to provide the necessary
transition and protection. Mechanical Interlocks are available for fixed and
draw out circuit breakers. The interlocks enable directly interlocking
breakers that are mounted side by side or in vertical stacks. The interlocks
consist of two components: (A) The factory-installed bracket fitted to the
breaker (fixed breakers) or the cassette (drawout breakers), and (B) The
field-installable interconnecting cables available in lengths of 1.0, 1.6, 2.0,
2.5, 3.0, 3.5 and 4.0m (ordered separately). Refer to Section 4 for
interlocking schemes.
Contact factory for availability.
®
G Circuit Breaker Application Guide
Section 5. Catalog Numbering Guide
Code
X
1
2
3
4
65

Advertisement

Table of Contents
loading

Table of Contents