Page 2
Symbols used Symbol Description Warning to proceed strictly in accordance with the information contained in the documentation in order to ensure the safety and full functionality of the device. Information particularly useful during installation and operation of the device. Information particularly useful during installation and operation of a type Ex device. Information on disposal of used equipment BASIC REQUIREMENTS AND SAFE USE - The manufacturer will not be liable for damage resulting from incorrect installation,...
SGE-25S ............10 ETTINGS OF PROBES 9.2. S SGE-25.SMART, SGE-25S.SMART ..............10 ETTINGS OF PROBES 9.3. SGE-25.SMART, SGE-25S.SMART. M ......... 10 EASUREMENT RANGES EFINITIONS 9.4. C ....................... 11 ONFIGURATION AND ALIBRATION 10. INSPECTIONS, REPAIRS AND SPARE PARTS ................11 10.1.
Page 4
Together with the probes ordered, the user will receive: User’s Manual numbered DTR.SG...04 with Appendix Ex, and also the Product Certificate. 5. Permitted input parameters of the SGE-25.SMART, SGE-25S.SMART, SGE-25C.SMART probes. (based on data from the KDB 09ATEX008 certificate and certification documentation.) -permitted input parameters for power supply with a linear characteristic.
DTR.SG...04 (ENG) Appendix Ex.03 (SGE–25.SMART, SGE–25S.SMART, SGE–25C.SMART) 6. Supply examples. Power supply with a “linear” characteristic may be e.g. a typical barrier with parameters: Ω Uo=28V Io=0.093A Rw=300 Example of practical provision of power supply for case: use the barrier with the parameters given above Fig.1.
DTR.SG...04 (ENG) APPENDIX Ex.04 (SGE–25, SGE–25S, SGE–25C) DTR.SG...04. Appendix Ex.04 (ENG) (SGE–25, SGE–25S, SGE–25C) 1453 HYDROSTATIC LEVEL PROBES type: SGE–25, SGE–25S, SGE–25C Ex VERSIONS Introduction 1.1 This “Appendix Ex.04” applies only to hydrostatic level probes SGE-25, SGE-25C and SGE-25S in Ex versions, marked on the rating plate as shown in 2.2 and denoted Ex in the Product Certificate.
Page 7
DTR.SG...04 (ENG) Appendix Ex.04 (SGE–25, SGE–25S, SGE–25C) 6. Supply examples Power supply with a linear characteristic may be e.g. a typical barrier with parameters: Ω Uo=28V Io=0.093A Rw=300 Example of practical provision of power supply for case: use the barrier with the parameters given above Fig.1.
(probes SGE-25, SGE-16, SGE-25C, SGE-25S) and a digital communi- cation signal in the „HART” system (probes SGE-25.SMART, SGE-25S.SMART),or in special versions into a 0÷10V signal transmitted in a three-wire system (applicable only to the SGE-25, SGE-25S, SGE-25C models).
500 V AC or 750 V DC Excess voltage protection see. 10.2.3. 5.1.5. SGE-25.SMART and SGE-25S.SMART . Permitted Environmental Conditions. Process temperature limit -30...80º C – for the basic range 0...10 m H -30...50º C – for the basic range 0...100 m H Maximum process temperature for Ex-version see “Appendix Ex.03 SGE–25.SMART,...
DTR.SG...04 (ENG) Long term stability 0,1% or 1 cm H 2 O for 1 year Thermal compensation range 0 ÷ 25º C – standard, -10 ÷ 70º C – for special version Process temperature limit -25 ÷ 50º C – for ranges > 20m H -25 ÷...
After processing, the digital signal is again converted into an analogue 4÷20mA current signal, with a superimposed digital communication signal. For communication with the probe via the signal line a special Aplisens communicator KAP is used. 6.3.2. The analog version (SGE-25, SGE-25S, SGE-25C and SGE-16 probes).
If the transmission line leads to remote premises via the open air, it is recommended that a terminal box, be fitted, e. g. the Aplisens type PP, in order to connect the probe’s cable to the remaining section of the transmission line.
This process and zero-point adjustment are called “Calibration”. 9.4.4. Configuration and Calibration of the probe are carried out using an Aplisens KAP communicator, certain Hart communicators or a PC with Hart/RS232 converter and Aplisens Raport-01 software. A description of the functions or the KAP communicator is contained in KAP Communicator Operating Manual, and information on the Hart/RS232 converter can be found on the Hart/RS232/01 Converter information sheet.
(e.g. monitor, regulator, controller). 10.1.3 . Check the „zero point” SGE-25.SMART, SGE-25S.SMART see 10.1.2. 10.2. Additional Inspections. If the probe is installed in a place where it might have been subject to mechanical damage, wearing cable covering, excess pressure, hydraulic impulses, sedimentation, crystallization or erosion of the diaphragm, or excess electrical voltage, inspections should be made as necessary.
+5° C and +40° C and relative humidity not greater than 85%. 12. GUARANTEE. The manufacturer guarantees the proper functioning of the probes SGE-25.SMART, SGE-25S.SMART, SGE-25, SGE-16, SGE-25C for a period of 24 months starting from the date of purchase (probe SGE-25S for a period of 12 months), as well as servicing carried out under the guarantee and following the guarantee period.
DTR.SG...04 (ENG) Special version of probe. Cable with additional Red or red/yellow wire Black or black/blue wire teflon covering Black or black/blue wire ∅ Capillary 2x0,5 Teflon tube Supporting handle (Not applicable to SGE-16) ∅ 25(SGE-25) ∅ 16(SGE-16) ∅ ∅ Zero Zero level...
DTR.SG...04 (ENG) Cord for earthing (do not using to mounting of probe) Set screw Steel band Cord for earthing Teflon tube Set screw Lifting handle (The probe suspend on a steel cable using the lifting handle.) SGE-25, SGE-25SMART SGE-25S, SGE-25S.SMART. Figure 4.
DTR.SG...04 (ENG) 15. APPENDIX 1. Testing of excess voltage protection elements (Not applicable to Ex version) Probe (not immersed) UZ power supply set to 50V DC Figure 5a. Testing the Transil diode connected between the wires. (Not applicable to Ex version) a) The results for an undamaged diode should be as follows: R=600 , UZ=24VDC - line current...