Error messages on the control panel

C
P
ODE
ROBABLE CAUSE
E7
Fan error
F1
Dirty Filter
F17
With automatic CO
The CO
sensor in the inlet duct is
2
not working.
Manual version 4.1 (26-07-2018)
Error codes register 217/ErrorFlags[1]
L
.
OGERROR
CSV
V
C
ALUE
ODE
16
F1
29
F17
For models with b-touch control panel
Some errors are displayed with a
screen of the b-touch panel.
n
n
W
HAT TO DO
1. Check the fans. If one or more fans do not work, please
check:
-
-
-
-
2. If these are in order, then replace the fan.
Replace the filters.
control:
1. Check the sensor's wiring and connection (connector
2
X377).
2. If these are in order, then replace the sensor.
D
ESCRIPTION
Filters must be replaced
Faulty CO
sensor
2
Note:
When the error message is touched, the screen
displays an explanation, together with a list of the
actions to be taken.
Note:
The message will disappear from the Home screen
when the error has been remedied.
the fan wiring;
the connections on the electronics module;
the transformer fuse;
the transformer itself.